Page 29

background image

Part Number 550-110-710/0107

9

GOLD CGi Gas-Fired Water Boiler — Boiler Manual

3 System or zone circulator
7 System temperature valves (see instructions to the

left for adjusting valves)

8 Blend temperature gauge
9 Relief valve
10 Automatic air vent (with diaphragm-type expan-

sion tank), or connect to tank fitting (closed-type

expansion tank).

DO NOT use an automatic air vent

when using closed-type expansion tank. It would

allow air to leave the system, causing waterlogging

of the expansion tank.

11 Fill valve
12 Diaphragm-type or bladder-type expansion tank,

if used (For closed-type expansion tank, pipe from

top of air separator to tank fitting as in

Figure 17,

page 1.)

Figure 24

System-bypass piping — Zoning with

zone valve or circulators, return water

130°F or higher — (Alternative to boiler-

bypass piping Figures 22 and 23)

Figure 25 Piping refrigeration systems

4e

Prevent chilled water from

entering boiler

Water piping — refrigeration system

Install boiler so that chilled medium is piped in parallel
with the heating boiler. Use appropriate valves to prevent
chilled medium from entering boiler. See Figure 18 for
typical installation of balancing valve and check valve.

If boiler is connected to heating coils located in air han-
dling units where they can be exposed to refrigerated
air, use flow control valves or other automatic means to
prevent gravity circulation during cooling cycle.

Piping — low temperature systems

(continued)

4d