beautypg.com

Venting — direct exhaust — components, Gold cgi gas-fired water boiler — boiler manual, Obtain vent system components – Weil-McLain GOLD CGI 550-110-710/0107 User Manual

Page 15

background image

Part Number 550-110-710/0107

15

GOLD CGi Gas-Fired Water Boiler — Boiler Manual

Venting — Direct exhaust — components

3c

Obtain vent system components

1. The following special gas vent systems comply with UL-138 and ULC-

S636 standards and are certified by CSA as the only systems suitable for

use with CGi boilers (all 3” diameter):
• Heat-Fab, Inc.

Saf-T Vent

®

• Flex-L International, Inc.

StaR-34

• Z-Flex®, Inc.

Z-Vent II

• ProTech Systems

FasNSeal™

Use only the vent starter of the same manufacturer as

the vent components. Do not mix components from

different systems. The vent system could fail, causing

flue gas spillage, resulting in severe personal injury or

death.

. Select vent method based on page 14 and installation requirements.
3. Refer to

Table 4

for maximum vent run lengths and number of elbows.

Do not exceed data in

Table 4

.

4. Select vent components from separate

CGi, Cgs & GV Vent Component

Supplement

. All components, including the vent starter, must be of

the same vent manufacturer. Do not mix components.

Table 4 Maximum vent length