GOLD CGi Gas-Fired Water Boiler — Boiler Manual

1

Boiler isolation (balancing) valves

2

Flow/check valve

3

System or zone circulator

4

System temperature gauges

5

Zone valve

6

Drain valve

7

System temperature valves (see in-

structions to the left for adjusting

valves)

8

Blend temperature gauge

9

Relief valve

10

Automatic air vent (with diaphragm-type expansion tank), or

connect to tank fitting (closed-type expansion tank).

DO NOT

use

an automatic air vent when using closed-type expansion tank. It

would allow air to leave the system, causing waterlogging of the

expansion tank.

11

Fill valve

12

Diaphragm-type or bladder-type expansion tank, if used (For

closed-type expansion tank, pipe from top of air separator to

tank fitting as in

Figure 17,

page 1).

13

Air separator and automatic vent, if used (Note that the fill valve

must always be connected to the expansion tank, regardless of

location of expansion tank, circulator or air separator.)

Figure 22

Boiler-bypass piping — Zoning with

circulators — (Alternative to primary/

secondary piping Figures 20 and 21)

Figure 23

Boiler-bypass piping — Zoning with

zone valves — (Alternative to primary/

secondary piping Figures 20 and 21)

Piping — low temperature systems

(continued)

4d