GOLD CGi Gas-Fired Water Boiler — Boiler Manual

16

Part Number 550-110-710/0107

Venting — direct exhaust — vent starter

3d

1. Select a vent pipe manufacturer and obtain all vent

components needed, based on boiler location and

venting method.

. You must use the vent starter made by the vent pipe

manufacturer. See separate

CGi, CGs & GV Vent

Component Supplement

, for part number of each

component, listed by vent manufacturer.

Use only the vent starter of the same

manufacturer as the vent compo-

nents. Do not mix components

from different systems. The vent

system could fail, causing flue gas

spillage, resulting in severe personal

injury or death.

3. Follow all applicable national, state, local or provin-

cial codes when venting the CGi boiler.

4. Connect vent starter to blower housing outlet as

shown in the

Figures 8

through

11

.

a. Do not mix components from different vent

manufacturers.

b. Maintain minimum ” clearance from com-

bustible materials to vent pipe.

c. Seal with sealant specified by vent pipe

manufacturer, using ³⁄₈" bead (not required for

FasNSeal™).

d. Tighten strap at band clamp screw until strap

is snug around blower housing.