beautypg.com

Piping — low temperature systems, Gold cgi gas-fired water boiler — boiler manual, Boiler-bypass piping method – Weil-McLain GOLD CGI 550-110-710/0107 User Manual

Page 26: Valve adjustment

background image

GOLD CGi Gas-Fired Water Boiler — Boiler Manual

6

Part Number 550-110-710/0107

BOILER-bypass piping

method

This piping method (

Figure 22

or

23

) is called a

boiler-

bypass

because part of the circulator flow is bypassed

around the boiler (through valve

7a

). This method

reduces the flow rate throughout the boiler, in order

to raise the average water temperature in the boiler

enough to prevent flue gas condensation. Boiler-bypass

piping is effective for some boilers — including the CGi

— provided the flow rates are adjusted according to the

instructions following.

Figures 22

and

23

are alternative piping suggestions

for

converted gravity

(large water content or steam

systems) or

radiant heating system

— for use when

primary/secondary piping can’t be applied. (

Figure 24

is another alternative, using system bypass in place of

boiler-bypass piping.

Figure 24

however, is not suitable

for radiant heating applications because it does not

protect the radiant system from possible high water

temperature.)
Boiler-bypass piping keeps system flow rate as high as

possible and temperature drop as low as possible, help-

ing to equalize the building heat distribution.

Temperature gauges

Gauge

4a

is optional if the bypass valves will be ad-

Piping — low temperature systems

4d

justed using cold (or room temperature) return water

to the boiler. (When setting the valves without gauge

4a

installed — using cold or room temperature water

— assume the return water temperature to be 60°F. Set

the valves so gauge

8

reads at least 10°F.

Gauge

4b

is optional on converted gravity systems,

but

required

on radiant heating systems — to display

the water temperature being supplied to the radiant

tubing.
Gauge

8

is

required

on all systems to assure reliable

adjustment of the bypass valves. The boiler-mounted

temperature/pressure gauge can be used if a separate

temperature gauge is not installed.

Valve adjustment

1. Start with valve

7a

fully closed and

7b

fully open.

. Gradually open valve

7a

while closing valve

7b

until the temperature at gauge

8

reads 60 °F higher

than gauge

4a

. A minimum 60°F temperature rise

through the boiler assures a low enough flow rate

and high enough average temperature to prevent

condensation even with low system return water

temperature.

3. Valve

7a

regulates the system flow rate, while valve

7b

regulates the boiler flow rate.

4. The boiler-mounted temperature/pressure gauge

may be used in place of a separate gauge

8

.

Failure to

prevent low return water temperature

to the boiler could cause corrosion of

the boiler sections or burners, resulting in severe personal injury, death or substantial
property damage.

Radiant heating system piping should include a means of

regulating the boiler return

water temperature

and the

system supply temperature

(such as provided by an

injec-

tion pumping control

).

Boiler return water temperature will be adequately controlled using the methods shown

in this manual provided the

system supply temperature

is

relatively constant.

DO NOT

apply the methods of this manual if the system is equipped with an

outdoor

reset control.

Instead,

provide controls and piping

which can

regulate the boiler re-

turn water temperature

at

no less than 130°F

regardless of system supply temperature.

Contact your Weil-McLain representative for suggested piping and control methods.

Failure to

prevent cold return water temperature

to the boiler could cause corrosion

damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.