beautypg.com

Start-up — operate boiler, Gold cgi gas-fired water boiler — boiler manual, Start the boiler – Weil-McLain GOLD CGI 550-110-710/0107 User Manual

Page 34: Check system and boiler

background image

GOLD CGi Gas-Fired Water Boiler — Boiler Manual

34

Part Number 550-110-710/0107

Start-up — operate boiler

7b

DO NOT

proceed with boiler

operation unless boiler and
system have been filled with
water and all instructions
and procedures of previous
manual sections have been
completed. Failure to do so
could result in severe personal
injury, death or substantial
property damage. Before start-
ing the boiler, do the follow-
ing:
• Read manual

Section 9

and

the

Operating instruction

procedure applicable for
the gas valve supplied on
the boiler (Section

9c

).

• Verify the boiler and system

are

full of water

.

• Verify the

Start-up prepa-

ration

procedures of

Sec-

tion 7

have been complet-

ed.

Start the boiler

• Follow the

Operating instructions

from Section

9c

to start the boiler.

• See

Section 7c

if boiler fails to start.

Check system and boiler

1.

Check system piping for leaks.

If found, shut down

boiler and repair immediately.

.

Vent air from system

using manual vents. Air in

the system will interfere with circulation and cause

heat distribution problems and noise.

3.

Inspect vent system

thoroughly for signs of

deterioration from corrosion, physical damage or

sagging. In addition — Check for gas-tight seal at

every connection and seam.

If you discover evidence of any

gas leak, shut down the boiler

at once. Find the leak source

with bubble test and repair

immediately. Do not start

boiler again until corrected.

Failure to comply could re-

sult in severe personal injury,

death or substantial property
damage.

Eliminate all system leaks.

Continual fresh makeup water
will reduce boiler life. Miner-
als can build up in sections,
reducing heat transfer, over-
heating cast iron, and causing
section failure.

Glycol or antifreeze leaks

around the boiler may result
in fire, causing severe personal
injury, death or substantial
property damage.

Do not use

petroleum-based

cleaning or sealing com-

pounds

in boiler system.

Severe damage to boiler will

occur, resulting in substantial

property damage.

Venting system must be sealed

gas-tight

to prevent flue gas spill-

age and carbon monoxide emissions

which will result in severe personal

injury or death.

4.

Check around the boiler

for gas odor following the

procedure of Section

7a

of this manual.

5.

Verify operation

per Section

7b

. Perform check-out

procedure in Section

8

, and fill in the

Installation

and service certificate

on the same page.