Installation & Servicing Instructions Rinnai E-Series

84

contact for return sensor T2 open

check the data

in Error mode

1 error
2 operational

status

3 supply temp.
4 return temp.
5 kW burner
6 % pump

check the wiring

the wiring is OK

but the error is

repeated

replace the

sensor

*= variable value

boiler data during error

1 = 37
2 = 00
3 = xx*
4 = -22
5 = 00
6 = xx*

check the wiring for the sensor to make sure
it is not broken

connect the wiring from the return sensor with
one another as a result of which Error 32
occurs

15.2.18 Error 37