Installation & Servicing Instructions Rinnai E-Series

82

shut down of return sensor T2

check the data

in Error mode

1 error
2 operational

status

3 supply temp.
4 return temp.
5 kW burner
6 % pump

check the wiring

the wiring is OK

but the error is

repeated

replace the

sensor

*= variable value

boiler data during error

1 = 32
2 = 00
3 = xx*
4 = 230
5 = 00
6 = xx*

check the wiring for the sensor

remove the plug from the return sensor as a
result of which Error 37 occurs

15.2.16 Error 32