Installation & Servicing Instructions Rinnai E-Series

81

internal shut down of supply sensor T1

check the data

in Error mode

1 error
2 operational
status
3 supply temp.
4 return temp.
5 kW burner
6 % pump

check the wiring

the wiring is OK

but the error is

repeated

replace the

sensor

*= variable value

boiler data during error

1 = 31
2 = 00
3 = 230
4 = xx*
5 = 00
6 = xx*

check the wiring for the sensor

remove the plug from the flow sensor as a
result of which Error 36 occurs

15.2.15 Error 31