Installation & Servicing Instructions Rinnai E-Series

31

In certain weather conditions condensation may also accumulate on the

outside of the air inlet pipe. Such conditions must be considered and where

necessary insulation of the inlet pipe may be required.

In cold and/or humid weather water vapor may condense on leaving the vent

terminal. The effect of such ‘water condensation’ must be considered.
The terminal must be located in a place not likely to cause a nuisance.
Use the Instructions of the Rinnai venting system for installation and service.
Cellular or Foam core PVC is not permitted for use with the boiler.

6.7.5

Dimensioning of the exhaust and air intake duct

The wall mounted boiler must be vented and supplied with combustion and

ventilation air as described in this section.

Ensure the vent and air piping and the combustion air supply comply with

these instructions regarding vent system, air system, and combustion air

quality.

Inspect finished vent and air piping thoroughly to ensure all are airtight and

comply with the instructions provided and with all requirements of applicable

codes.

Failure to provide a properly installed vent and air system may cause severe

personal injury or death.

Use only the material listed in Rinnai's vent documentation for vent pipe, and

fittings. Failure to comply could result in severe personal injury, death or

substantial property damage.

Installation must comply with local requirements and with the National Fuel

Gas Code, ANSI Z223.1 for U.S installations or CSA B 149.1 for Canadian

installations.

For closet and alcove installation, CPVC material (instead of PVC) must be

used in a closet/alcove structure. Failure to follow this warning could result

in fire, personal injury, or death.

All vent pipes must be connected and properly supported, and the exhaust

must be pitched a minimum of a 1/4” inch per foot back to the boiler (to allow

drainage of condensate). Please refer to the venting manufacturer's manual

to see if a larger pitch is required for specific venting sytems.

For the Room Air System, combustion air piping from the outside MUST BE

used. Use of combustion air from indoor rooms using louvers, plenums, or

any other devices is not authorized.

See the Rinnai Boiler Applications Manual for further information on venting.