Installation & Servicing Instructions Rinnai E-Series
83
contact for supply sensor T1 open
check the data
in Error mode
1 error
2 operational
status
3 supply temp.
4 return temp.
5 kW burner
6 % pump
check the wiring
the wiring is OK
but the error is
repeated
replace the
sensor
*= variable value
boiler data during error
1 = 36
2 = 00
3 = -22
4 = xx*
5 = 00
6 = xx*
check the wiring for the sensor
remove the plug from the flow sensor as a
result of which Error 31 occurs
15.2.17 Error 36