Installation & Servicing Instructions Rinnai E-Series

32

6.7.6 Combustion air and vent piping lengths.

In the table below you find the maximum equivalent pipe length of the vent/air system

based on 3" diameter. These lengths are for single pipe (room air), twin pipe, and
concentric venting systems.

Calculation of equivalent length vent system

Choose the vent type and fill out the corresponding table.

* When determining equivalent combustion air and vent length, add 6 feet for each
90° elbow, 3 feet for each 45° elbow, 5 feet for the concentric terminal in the Parallel
System, and 2 feet for the concentric terminal in the Concentric System .

Example of calculation:

Twin tube (parallel) with terminal

Combustion air length

: 24 ft

with elbow 3 x 90°

Vent length

: 24 ft

with elbow 2 x 90°, elbow 2 x 45°

Calculation:

Equivalent Air Length

: (24+3x6+2) x 0.5

= 23 ft

Equivalent Vent Length

: (24+2x6+2x3+2) x 0.5

= 23 ft +Total

= 46 ft.

Equivalent vent length

table 9

Boiler type

3” Max Vent equivalent length

3” Max Air equivalent length

E75

100 feet

100 feet

E110

100 feet

100 feet

Parallel system

Length tube

Number of

elbows 90°

x 6*

Number of

elbows 45°

x 3*

Concentric

terminal

A

dd 5 ft.*

Total

Multiply with

factor

Equivalent

length

Combustion air

ft

ft

ft

ft

ft

0.5

ft

Vent

ft

ft

ft

ft

ft

0.5

ft
ft

Total equivalent length

Concentric system

Length concentric

tube, boiler to roof

horizontal

Number of

elbows 90°

x 6*

Number of

elbows 45°

x 3*

Concentric

terminal

A

dd 2 ft.*

Total

Multiply with

factor

Total equivalent

length

ft

ft

ft

ft

ft

1.0

ft