beautypg.com

4 recommended vent/air intake terminal position – Rinnai E75CN User Manual

Page 29

background image

Installation & Servicing Instructions Rinnai E-Series

29

6.7.4

Recommended vent/air intake terminal position

Terminals should be positioned as to avoid products of combustion entering openings into buildings or other vents.

Maintain 12” of clearance

above the highest

anticipated snow level

or grade or, whichever is

greater. Please refer to

your local codes for the

snow level in your area.

clearances of venting system terminals

table 6

Terminal positions

figure 14

[1] A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves
both dwellings.

[2] Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

* For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearances are in accordance with local installation codes and the
requirements of the gas supplier.

Ref

Description

Canadian Installations - Direct Vent

and non Direct Vent

US Installations Direct Vent

US Installations

non Direct Vent

A

Clearance above grade, veranda, porch,
deck, or balcony

12 inches (30 cm)

12 inches (30 cm)

12 inches (30 cm)

B

Clearance to window or door that may
be opened

6 inches (15 cm) for appliances < 10,000

Btuh (3 kW), 12 inches (30 cm) for ap-

pliances > 10,000 Btuh (3 kW) and <

100,000 Btuh (30 kW), 36 inches (91 cm)

for appliances > 100,000 Btuh (30 kW)

6 inches (15 cm) for appliances < 10,000

Btuh (3 kW), 9 inches (30 cm) for ap-

pliances > 10,000 Btuh (3 kW) and <

50,000 Btuh (30 kW), 12 inches (91 cm)

for appliances > 50,000 Btuh (30 kW)

4 feet (1.2 m) below or to

side of opening; 1 foot (300

mm) above opening

C

Clearance to permanently closed window

*

*

*

D

Vertical clearance to ventilated sof-

fit, located above the terminal within a
horizontal distance of 2 feet (61 cm) from
the center line of the terminal

*

*

*

E

Clearance to unventilated soffit

*

*

*

F

Clearance to outside corner

*

*

*

G Clearance to inside corner

*

*

*

H

Clearance to each side of center line ex-
tended above meter/regulator assembly

3 feet (91 cm) within a height 15 feet (4.5

m) above the meter/regulator assembly

*

*

I

Clearance to service regulator vent outlet

36 inches (91 cm)

*

*

J

Clearance to nonmechanical air supply
inlet to building or the combustion air inlet
to any other appliance

6 inches (15 cm) for appliances < 10,000

Btuh (3 kW), 12 inches (30 cm) for ap-

pliances > 10,000 Btuh (3 kW) and <

100,000 Btuh (30 kW), 36 inches (91 cm)

for appliances > 100,000 Btuh (30 kW)

6 inches (15 cm) for appliances < 10,000

Btuh (3 kW), 9 inches (30 cm) for ap-

pliances > 10,000 Btuh (3 kW) and <

50,000 Btuh (30 kW), 12 inches (91 cm)

for appliances > 50,000 Btuh (30 kW)

4 feet (1.2 m) below or to

side of opening; 1 foot (300

mm) above opening

K

Clearance to a mechanical air supply
inlet

6 feet (1.83 m)

3 feet (91 cm) above if within 10 feet (3

m) horizontally

3 feet (91 cm) above if wit-

hin 10 feet (3 m) horizontally

L

Clearance above paved sidewalk or
paved driveway located on public
property

7 feet (2.13 m) [1]

*

7 feet (2.13 m)

M Clearance under veranda, porch, deck,

or balcony

12 inches (30 cm) [2]

*

*

This manual is related to the following products: