beautypg.com

Rinnai E75CN User Manual

Page 35

background image

Installation & Servicing Instructions Rinnai E-Series

35

OUTLET AIR DUCT

INLET AIR DUCT

Gas Vent / Boiler Exhaust

BOILER

12in. MAX

12in. MAX

PERMANENT

OPENINGS

BOILER

10"

(250mm)

12"

(300mm)

Louvers and grills figure 17

Confined Space:
(Small Room, Closet, Alcove, Utility Room, Etc.)

A confined space is defined in the NFPA #54 as "a space whose volume is less than
50 cubic feet per 1000 Btu/hr (4.8 m3 per kW per hour) of the aggregate input rating

of all appliances installed in that space." A confined space must have two combustion
air openings. Size the combustion air openings based on the BTU input for all gas
utilization equipment in the space and the method by which combustion air is supplied:

Using indoor air for combustion

Using outdoor air for combustion

Louvers and Grills

When sizing the permanent opening as illustrated in figure 17, consideration must be
taken for the design of the louvers or grills to maintain the required free area required
for all gas utilizing equipment in the space. If the free area of the louver or grill design
is not available, assume wood louvers will have 25% free area and metal louvers or
grills will have 75% free area. Under no circumstance should the louver, grill or screen
have openings smaller than ¼”.

Example:
Wood: 10 in x 12 in x 0.25 = 30 in2
Metal: 10 in x 12 in x 0.75 = 90 in2

Location
To maintain proper circulation of combustion air two permanent openings (one up-

per, one lower) must be positioned in confined spaces. The upper shall be within 12

inches of the confined space and the lower opening shall be within 12 inches of the

bottom of the confined space. Openings must be positioned as to never be obstructed.

Combustion air provided to the appliance should not be taken from any area of the
structure that may produce a negative pressure (i.e. exhaust fans, powered ventila-
tion fans).

This manual is related to the following products: