Regency

®

P40-1 Direct Vent Gas Fireplace

19

INST

ALLA

TION

INSTALLATION

H

H1

V

Horizontal Venting with Two (2) 90

o

Elbows

Horizontal Venting with Three (3) 90

o

Elbows

One 90

o

elbow = Two 45

o

elbows.

One 90

o

elbow = Two 45

o

elbows.

Option V

H + H1

A)

2' Min. 2' Max.

B)

3' Min. 5' Max.

C)

4' Min. 6' Max.

D)

5' Min. 7' Max.

E)

6' Min. 8' Max.

W i t h t h e s e o p t i o n s ,
maximum total pipe length
is 30 feet with minimum
of 6 feet total vertical
and maximum 8 feet total
horizontal.

Option V

H V + V1 H + H1

A)

0' Min. 1' Max. 1' Min. 1' Max.

B)

1' Min. 2' Max. 3' Min. 3' Max.

C)

2' Min. 2' Max. 5' Min. 4' Max.

D)

3' Min. 2' Max. 7' Min. 5' Max.

E)

4' Min. 3 Max. 9' Min. 6' Max.

F)

5' Min. 4' Max. 10' Min. 7' Max.

G)

6' Min. 5' Max. 11' Min. 8' Max.

H)

7' Min. 6' Max. 12' Min. 9' Max.

With these options,
max. total pipe length
is 30 feet with min. of
12 feet total vertical
and max. 9 feet total
horizontal.

Please note min. 1
foot between 90

o

elbows is required.

VENT RESTRICTOR SETTING:
When total vertical exceeds total horizontal by 2x the vent
restrictor setting is set to 1.

Please note minimum 1 foot between 90

o

elbows is

required.

VENT RESTRICTOR SETTING:
When total vertical exceeds total horizontal by 3x the vent restrictor
setting is set to 1.