W write system variable, Z reset, Write system variable – Parker Products ViX250AE User Manual
Page 108: Reset
6. COMMAND REFERENCE
101
W
Write system variable
Syntax
aW(system_variable,value)
Description
The W command allows you to set a specified system variable to a
particular value.
Refer to the table of system variables for more information.
Properties
Immediate not saved by SV
Example
Set system variable TL (Tracking Limit) to 4000
Report the current value of system variable TL
The controller responds with......................................
2W(TL,4000)
2R(TL)
*4000
Note
The drive will need to be de-energised before certain system variables can
be written to.
See also R command.
See table of allowable variables for individual parameter details.
Z
Reset
Syntax
Units
Range of ‘n’
Default
See also
aZ
-
-
-
SV
Description
The Z command resets the drive. This is similar to power cycling the drive.
Wait 1-2 seconds before sending any other command following a Z.
Following the issue of the Z command, any configuration which has been
made but not saved, with the SV command, will be lost.
Properties
Immediate, not saved by SV
Example
To reset all drives, type....................................................
0Z