Daylight saving time

The daylight saving time changeover is automatically performed by the device at
the parameterized times.

/Time/Advanced/Daylight Saving Time (0.09.07) parameter

With the setting "enable = no", the time changeover is suppressed and the plant
is operated with standard time.

The calendrical regulation for the daylight saving time changeover can be speci-
fied worldwide via a parameter.

Leap seconds

Use the /Time/Advanced/Leap Seconds[20] (0.09.05) parameter to specify the
calendar of leap seconds.

9.3.2

Synchronization

Synchronization status

You can read out different information about the current synchronization status
via the /Synchronization/Status of Synchronization (0.09.09) parameter.

Protected synchronization

If a discontinuity of more than 5 s occurs in the external synchronization, the pro-
tected synchronization is activated. The synchronization is suppressed and an
alarm issued which is present as long as there is a discontinuity in the external
synchronization.

The pending synchronization suppression can be ignored once and the "Pro-
tected synchronization" alarm cleared with the parameter entry /Synchroniza-
tion/Advanced/Protected Synchronization/ignore /clear alarm (0.09.12) = "yes".

Note

The preset changeover times correspond to the present valid regulations of the
European Community.

Notice

This initiates an unconditional synchronization to the external time and an incon-
sistency in the time distribution to the plant can result.

If required, disconnect the active external synchronization first or delete the server
address for the NTP client operation from the /NTP Client/NTP Server List[4]
(0.18.02) parameter.