13 technical data, Technical data – Siemens SICLOCK TC 400 User Manual
Page 107
13-105
© Siemens AG 2007 All Rights Reserved
SICLOCK
®
TC 400
Technical Data
13
Table 13-1
Technical data of the SICLOCK TC 400
Dimensions
180.0 x 88.9 x 47.0 (WxHxD in mm)
Weight
Approximately 750 g
Supply voltage
24 VDC (-15% to +20%) at X1
Power supply
Continuous current max. 0.7 A
Transient voltage interruption
Max. 3 ms (at 20.4 V to 28.8 V)
Power consumption
Max. 15 W
Power loss
Typ. 7.5 W
Fuse (external)
1 A time-lag
Degree of protection
IP 20
Mounting type
35 mm DIN rail
DIN rail EN 50022-35 (15 mm high) or SIMATIC standard mounting rail
Safety
Product standard
EN 61131-2 (environment)
Test voltage
Circuits with nominal voltage Ue <50 V relative to other circuits or
ground, test voltage 500 VDC
Protection class
Protection class III according to EN 60536
Electrical safety
EN 60950-1
Time properties
Accuracy with regard to the
GPS signal
< 50 µs
Accuracy with regard to the
DCF77 signal
< 1000 µs
Accuracy if GPS signal fails
< 50x10
-9
Accuracy if DCF77 signal fails
< 1x10
-6
Accuracy if power supply fails
< 4x10
-6
Time correction through
microstepping
< 50 µs/s
Jitter during GPS operation
< 200 ns/s
Reserve power
See battery
Battery
Service life during operation
> 12 years
Service life during storage, dis-
connected
> 12 years