beautypg.com

13 technical data, Technical data – Siemens SICLOCK TC 400 User Manual

Page 107

background image

13-105

© Siemens AG 2007 All Rights Reserved
SICLOCK

®

TC 400

Technical Data

13

Table 13-1

Technical data of the SICLOCK TC 400

Dimensions

180.0 x 88.9 x 47.0 (WxHxD in mm)

Weight

Approximately 750 g

Supply voltage

24 VDC (-15% to +20%) at X1

Power supply

Continuous current max. 0.7 A

Transient voltage interruption

Max. 3 ms (at 20.4 V to 28.8 V)

Power consumption

Max. 15 W

Power loss

Typ. 7.5 W

Fuse (external)

1 A time-lag

Degree of protection

IP 20

Mounting type

35 mm DIN rail
DIN rail EN 50022-35 (15 mm high) or SIMATIC standard mounting rail

Safety

Product standard

EN 61131-2 (environment)

Test voltage

Circuits with nominal voltage Ue <50 V relative to other circuits or
ground, test voltage 500 VDC

Protection class

Protection class III according to EN 60536

Electrical safety

EN 60950-1

Time properties

Accuracy with regard to the
GPS signal

< 50 µs

Accuracy with regard to the
DCF77 signal

< 1000 µs

Accuracy if GPS signal fails

< 50x10

-9

Accuracy if DCF77 signal fails

< 1x10

-6

Accuracy if power supply fails

< 4x10

-6

Time correction through
microstepping

< 50 µs/s

Jitter during GPS operation

< 200 ns/s

Reserve power

See battery

Battery

Service life during operation

> 12 years

Service life during storage, dis-
connected

> 12 years