Connecting
6-35
© Siemens AG 2007 All Rights Reserved
SICLOCK
®
TC 400
6.3
Connecting the external synchronization
The signal of the connected radio clock is detected automatically and displayed
in the /Inputs/Input 1/Status (0.20.02) parameter (or /Inputs/Input 2/Status
(0.21.02) parameter).
Figure 6-2 Circuit diagram for a passive and an active radio clock
Table 6-1
Terminal assignment of the radio clock inputs
Terminal
Designation
X2-7
RADIO CLOCK GND
X2-8
RADIO CLOCK 1A
X2-9
RADIO CLOCK 1B
X2-10
RADIO CLOCK 2A
X2-11
RADIO CLOCK 2B
X2-8
X2-9
48 V
X2-7
passive
Radio Clock 1
X2-8
X2-9
48 V
X2-7
active
Radio Clock 1
passive
Radio Clock 2
X2-10
X2-11
48 V
X2-10
X2-11
48 V
active
Radio Clock 2
Note
If you are operating two radio clocks, connect the preferred model to RADIO
CLOCK 1.