beautypg.com

Ancb leds description and operations, Continued – Siemens ADVANCE NETWORK COMMUNICATIONS BOARD/DATANET 2000592-001 User Manual

Page 60

background image

ANCB LEDs Description and Operations,

Continued

Figure 4-2 shows the edge visible LEDs on the ANCB. The LED labels
are silk-screened adjacent to each LED on the ANCB.

Figure 4-2: ANCB/DN LED
Indicators

CL

Use the following Table 4-1 to determine the error condition. FAULT
errors can only be cleared with a board reset.

Table 4-1: Error Codes

NUMBER

of Blinks

Type of Error

Corrective Action

1

RAM FAILURE

Replace Board

2

FLASH FAILURE

Reload Firmware or
Replace Board

3

ETHERNET FAILURE

Replace Board

4

DataNET FAILURE

Replace Board

6

DUPLICATE IP

Change Board IP address

8

WRONG LOOP

Change Loop Number

9

WRONG JUMPER
CONFIGURATION

Check J10 and J11
Connections

10

DUPLICATE UNIT NUMBER

Change Unit Number

50

Troubleshooting

2000592-001