FUJITSU M5000 User Manual
Page 209
Chapter 12
CPU Module Replacement 12-13
13. Continue with the appropriate installation procedure:
■
If you are adding a new SPARC64 VII/SPARC64 VII+ –equipped CPU module to a
domain configured with SPARC64 VI processors, continue with
SPARC64 VII/SPARC64 VII+ CPU Module to a Domain Configured With
SPARC64 VI” on page 12-13
■
If you are upgrading an existing SPARC64 VI CPU module in an existing domain
to SPARC64 VII/SPARC64 VII+ processors, continue with
“Upgrading a SPARC64 VI CPU Module to SPARC64 VII/SPARC64 VII+ on an
Existing Domain” on page 12-15
.
▼ Adding a SPARC64 VII/SPARC64 VII+ CPU
Module to a Domain Configured With
SPARC64 VI
This procedure must be preceded by
“Preparing to Add SPARC64 VII/SPARC64 VII+
Processors to an Existing Domain” on page 12-11
. If you have not completed that
procedure, do so before continuing.
1. Install the CPUM in the server.
For instructions, refer to the “CPU Module Replacement,” chapter in the SPARC
Enterprise M4000/M5000 Servers Service Manual. Note that this procedure involves
powering down the entire server.
Caution –
After installing the CPU module, you must reconnect the power cable to
the power supply.
2. Log in to the XSCF again, using an account with platadm or fieldeng
privileges.
Perform an initial diagnosis of the newly installed CPU module.
The following example shows a test after adding PSB#01:
XSCF> testsb 01
XSCF> testsb 01
Initial diagnosis is about to start. Continue? [y|n] : y
Initial diagnosis is executing.
Initial diagnosis has completed.
XSB Test Fault
---- ------- --------
01 Passed Normal