1 accessing the 60-mm fan module, Accessing the 60-mm fan module – FUJITSU M5000 User Manual
Page 168
10-4
SPARC Enterprise M4000/M5000 Servers Service Manual • December 2010
10.1.1
Accessing the 60-mm Fan Module
1. From the XSCF Shell prompt, use the replacefru command to disable the fan
to be removed.
The replacefru command is menu-driven. replacefru will continue while the
fan is removed and then test the fan. Refer to
Section 4.3.1, “Removing and Replacing
for more information.
Caution –
To prevent the equipment rack from tipping over, you must deploy the
antitilt feature, if applicable, before you slide the server out of the equipment rack.
Caution –
When drawing out the M4000/M5000 server to the front, release the cable
tie holding the PCI cables on the rear of the server.
2. Deploy the rack’s antitilt features (if applicable) and slide the server out of the
equipment rack.
See
Section 5.1.1, “Sliding the Server Out of the Equipment Rack” on page 5-2
.
Caution –
Use proper ESD grounding techniques when handling components. See
Section 1.1, “Safety Precautions” on page 1-1
.
XSCF> replacefru