beautypg.com

FieldServer Metasys N2 FS-8700-19 User Manual

Page 50

background image

FS-8700-19_Metasys_N2 Driver Manual

Page 50 of 51

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]

Appendix E. Error Messages

Error Message

Description and Action

MN2:#01 WARN.
Server_Hold_Timeout is
%0.3fs
For N2Open Slave
typical value is %0.3fs

Typically N2open Clients are configured to timeout after 200ms. If a
FieldServer is configured as a Server the Server_Hold_Timeout time
should be set to 0.175s or less otherwise the response will be suppressed.
This message is printed if the Server_Hold_Timeout is set for >0.175s.

If the Client’s timeout is >200ms this message may be ignored.