beautypg.com

FieldServer Metasys N2 FS-8700-19 User Manual

Page 17

background image

FS-8700-19_Metasys_N2 Driver Manual

Page 17 of 51

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]

5.2.

Server Side Node Descriptors

Section Title

Nodes

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32
alphanumeric
characters

Node_ID

MetasysN2 station address of physical
Server node

1-255

Protocol

Specify protocol used

Metasys_N2

Server_Hold_Timeout*

Specifies time FieldServer will reserve
Server side connection while waiting for the
Client side to update data in Data_Array

< 0.175s

5

Node_Type*

Identify type of device

This parameter need not be specified. The
Server side of the driver can only operate
as an N2 Server and the option for setting it
to N2Open is purely for backward
compatibility.

N2OpenServer,
N2Open

Example

// Server Side Nodes

Nodes

Node_Name,

Node_ID,

Protocol

PLC 1,

1,

Metasys_N2

5

Can be set to >0.175s if the Client has bee set to timeout after >200ms. Refer to Appendix E for more

information.