FS-8700-19_Metasys_N2 Driver Manual

Page 35 of 51

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]

PAGE 0

Item
DEC

Item
HEX

Signal Condition Read/Write

Johnson
Tag

Description

89

59 Byte

Write

EF3@

External forcing logic control
connection

90 5A

Byte

Write

TYPE3

Controller type

91 5B

FP

Write

LS3

Local setpoint

92 5C

FP

Write

PB3

Proportional band

93 5D

FP

Write

TI3

Reset action

94 5E

FP

Write

TD3

Rate action

95 5F

FP

Write

HL3

Upper limit of the control output

96

60 FP

Write

LL3

Lower limit of the control output

97

61 FP

Write

BS3

Change of setpoint during STAND-BY

98

62 FP

Write

BO3

Change of setpoint during OFF

99

63 FP

Write

AD3

Deviation alarm

100

64 Byte

Write

PV4@

Process variable connection

101

65 Byte

Write

RS4@

Remote setpoint connection

102

66 Byte

Write

RV4@

Reference variable connection

103

67 Byte

Write

PB4@

Proportional band connection

104

68 Byte

Write

OF4@

OFF mode logic control connection

105

69 Byte

Write

SB4@

STAND-BY mode logic control
connection

106 6A

Byte

Write

RA4@

Reverse action logic control connection

107 6B

Byte

Write

EF4@

External forcing logic control
connection

108 6C

Byte

Write

TYPE4

Controller type

109 6D

FP

Write

LS4

Local setpoint

110 6E

FP

Write

PB4

Proportional band

111 6F

FP

Write

TI4

Reset action

112

70 FP

Write

TD4

Rate action

113

71 FP

Write

HL4

Upper limit of the control output

114

72 FP

Write

LL4

Lower limit of the control output

115

73 FP

Write

BS4

Change of setpoint during STAND-BY

116

74 FP

Write

BO4

Change of setpoint during OFF

117

75 FP

Write

AD4

Deviation alarm

118

76 Byte

Write

PV5@

Process variable connection

119

77 Byte

Write

RS5@

Remote setpoint connection

120

78 Byte

Write

RV5@

Reference variable connection

121

79 Byte

Write

PB5@

Proportional band connection

122 7A

Byte

Write

OF5@

OFF mode logic control connection

123 7B

Byte

Write

SB5@

STAND-BY mode logic control
connection

124 7C

Byte

Write

RA5@

Reverse action logic control connection

125 7D

Byte

Write

EF5@

External forcing logic control
connection

126 7E

Byte

Write

TYPE5

Controller type

127 7F

FP

Write

LS5

Local setpoint

128

80 FP

Write

PB5

Proportional band

129

81 FP

Write

TI5

Reset action

130

82 FP

Write

TD5

Rate action

131

83 FP

Write

HL5

Upper limit of the control output

132

84 FP

Write

LL5

Lower limit of the control output

133

85 FP

Write

BS5

Change of setpoint during STAND-BY

134

86 FP

Write

BO5

Change of setpoint during OFF