beautypg.com

Appendix c.2. hardware connections, Appendix c.3. configuration settings – FieldServer Metasys N2 FS-8700-19 User Manual

Page 25

background image

FS-8700-19_Metasys_N2 Driver Manual

Page 25 of 51

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]

Appendix C.2. Hardware connections

The FS-8917-16 pigtail cable is typically used for this port arrangement. Connection is
depicted in the following diagram.

FS-8917-16

FS-X20

SERIAL

+

-

G

ORANGE/WHITE

(RJ45-08)

BROWN

(RJ45-01)

BLUE/WHITE

(RJ45-04)

RJ45 Male Modular

Jack

1

2

3

4

5

6

7

8

RJ45 M ale M odular Jack

1

2

3

4

5

6

7

8

RJ45 Female M odular Jack

Appendix C.3. Configuration Settings

• The Port address in the Configuration needs to be set to R1 instead of P1.
• Line_Drive_On and Line_Drive_Off need to be defined in the connections section of the

configuration file. These need to be set to at least 0.001s. Refer to Sections 4.2 and 5.1
for more information.