Programmable Module Type

Relative Item

Signal Condition

Read/Write

Johnson Tag

Description

57

FP

Write

PMK32

Module constant - K32

58

FP

Write

PMK33

Module constant - K33

59

FP

Write

PMK34

Module constant - K34

60

FP

Write

PMOU1

Output channel 1

61

FP

Write

PMOU2

Output channel 2

62

FP

Write

PMOU3

Output channel 3

63

FP

Write

PMOU4

Output channel 4

64

FP

Write

PMOU5

Output channel 5

65

FP

Write

PMOU6

Output channel 6

66

FP

Write

PMOU7

Output channel 7

67

FP

Write

PMOU8

Output channel 8

68

FP

Write

PMAX1

Auxiliary output 1

69

FP

Write

PMAX2

Auxiliary output 2

70

Byte

Write

PMHDC

Hold mode control/status

71

Byte

Write

PMDO

Logic output control and status

72

Word

Read

PMST

Programmable module status

73

LONG

Write

PMAC1

Accumulator channel 1

74

LONG

Write

PMAC2

Accumulator channel 2

75

LONG

Write

PMAC3

Accumulator channel 3

76

LONG

Write

PMAC4

Accumulator channel 4

77

LONG

Write

PMAC5

Accumulator channel 5

78

LONG

Write

PMAC6

Accumulator channel 6

79

LONG

Write

PMAC7

Accumulator channel 7

80

LONG

Write

PMAC8

Accumulator channel 8

Analog Input Modules

Relative Item

Signal Condition

Read/Write

Johnson Tag

Description

0

Word

Write

AIT

Analog inout type

1

FP

Write

HR

High range input

2

FP

Write

LR

Low range input

3

FP

Write

HIA

High alarm limit

4

FP

Write

LOA

Low alarm limit

5

FP

Write

FTC

Filter constant

6

FP

Write

ADF

Differential on alarm limit (units)

7

FP

Read

AI

Analog input value

8

FP

Read

AI%

Analog input %

9

FP

Read

ADC

Analog input in counts

10

Byte

Read

AIST

Analog input status

Analog Output Modules

Relative Item

Signal Condition

Read/Write Johnson Tag

Description

0

Byte

Write

AOT

Analog output type

1

Word

Write

AO@

Source of analog output module

2

Word

Write

AOF@

Output forcing logic connection

3

FP

Write

HRO

Output high range

4

FP

Write

LRO

Output low range

5

FP

Write

OFL

Output % value in forcing mode

6

FP

Write

OUT

Output module output value %

7

Byte

Write

AOC

Analog output control and status

8

FP

Write

HLO

Output high limit

9

FP

Write

LLO

Output low limit

10

Word

Write

INC@

DDC increase logic connection

11

Word

Write

DEC@

DDC decrease logic connection

12

Word

Write

ENL@

Limit function enable logic connection

Digital Output Modules

Relative Item

Signal Condition

Read/Write Johnson Tag