FieldServer Metasys N2 FS-8700-19 User Manual
Page 29
![background image](/manuals/104542/29/background.png)
FS-8700-19_Metasys_N2 Driver Manual
Page 29 of 51
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]
Programmable Module Type
Relative Item
Signal Condition
Read/Write
Johnson Tag
Description
57
FP
Write
PMK32
Module constant - K32
58
FP
Write
PMK33
Module constant - K33
59
FP
Write
PMK34
Module constant - K34
60
FP
Write
PMOU1
Output channel 1
61
FP
Write
PMOU2
Output channel 2
62
FP
Write
PMOU3
Output channel 3
63
FP
Write
PMOU4
Output channel 4
64
FP
Write
PMOU5
Output channel 5
65
FP
Write
PMOU6
Output channel 6
66
FP
Write
PMOU7
Output channel 7
67
FP
Write
PMOU8
Output channel 8
68
FP
Write
PMAX1
Auxiliary output 1
69
FP
Write
PMAX2
Auxiliary output 2
70
Byte
Write
PMHDC
Hold mode control/status
71
Byte
Write
PMDO
Logic output control and status
72
Word
Read
PMST
Programmable module status
73
LONG
Write
PMAC1
Accumulator channel 1
74
LONG
Write
PMAC2
Accumulator channel 2
75
LONG
Write
PMAC3
Accumulator channel 3
76
LONG
Write
PMAC4
Accumulator channel 4
77
LONG
Write
PMAC5
Accumulator channel 5
78
LONG
Write
PMAC6
Accumulator channel 6
79
LONG
Write
PMAC7
Accumulator channel 7
80
LONG
Write
PMAC8
Accumulator channel 8
Analog Input Modules
Relative Item
Signal Condition
Read/Write
Johnson Tag
Description
0
Word
Write
AIT
Analog inout type
1
FP
Write
HR
High range input
2
FP
Write
LR
Low range input
3
FP
Write
HIA
High alarm limit
4
FP
Write
LOA
Low alarm limit
5
FP
Write
FTC
Filter constant
6
FP
Write
ADF
Differential on alarm limit (units)
7
FP
Read
AI
Analog input value
8
FP
Read
AI%
Analog input %
9
FP
Read
ADC
Analog input in counts
10
Byte
Read
AIST
Analog input status
Analog Output Modules
Relative Item
Signal Condition
Read/Write Johnson Tag
Description
0
Byte
Write
AOT
Analog output type
1
Word
Write
AO@
Source of analog output module
2
Word
Write
AOF@
Output forcing logic connection
3
FP
Write
HRO
Output high range
4
FP
Write
LRO
Output low range
5
FP
Write
OFL
Output % value in forcing mode
6
FP
Write
OUT
Output module output value %
7
Byte
Write
AOC
Analog output control and status
8
FP
Write
HLO
Output high limit
9
FP
Write
LLO
Output low limit
10
Word
Write
INC@
DDC increase logic connection
11
Word
Write
DEC@
DDC decrease logic connection
12
Word
Write
ENL@
Limit function enable logic connection
Digital Output Modules
Relative Item
Signal Condition
Read/Write Johnson Tag
Description