FieldServer Metasys N2 FS-8700-19 User Manual
Page 45
FS-8700-19_Metasys_N2 Driver Manual
Page 45 of 51
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]
Input Output Config Parameters
Relative Item Signal Condition Read/Write Johnson Tag Description
W(14)
Read
Reset Cycle indication
W(15)
Read
00 = Power Up Reset
01 = External Reset
10 = Oscillator Failure
W(16)
Read
11 = Watchdog Reset
133
Word
R/W
TCS2
TC9100 Controller Options
W(1)
00 Select Analog Input 1 ADC
to
W(2)
11 Select Analog Input 4 ADC
W(3)
TM9100 does not overrd the proc Variable
W(4)
Half Alternate Mode Timing
W(5)
0 = Celsius 1 = Fahrenheit
W(6)
0 = 50 Hz 1 = 60 Hz Power Line
W(7)
Enable Facilitator Mode
W(8)
TRIAC7 is ON if mode is Comfort
W(9)
Digital Input #1 Mode
000 = Not used
001 = Window Open
010 = Occupancy Sensor
011 = Air Quality Sensor
100 = Reverse Action
W(11)
101 = Intrusion Alarm
W(12)
Negate Digital Input #1
W(13)
Digital Input #2 Mode
000 = Not used
001 = Window Open
010 = Occupancy Sensor
011 = Air Quality Sensor
100 = Reverse Action
W(15)
101 = Intrusion Alarm
W(16)
Negate Digital Input #2
134
Word
R/W
TCS3
Enable Jumper Options
W(1)
Enable Integral Zeroing Loop #1
W(2)
Enable Integral Zeroing Loop #2
W(3)
Enable Integral Zeroing Loop #3
W(4)
Enable Integral Zeroing Loop #4
W(5)
Enable Integral Zeroing Loop #5
W(6)
Enable Integral Zeroing Loop #6
W(7)
Not used
W(8)
Not used
W(9)
Enable Gain Doubling Loop #1
W(10)
Enable Gain Doubling Loop #2
W(11)
Enable Gain Doubling Loop #3
W(12)
Enable Gain Doubling Loop #4
W(13)
Enable Gain Doubling Loop #5
W(14)
Enable Gain Doubling Loop #6
135
Byte
Write
TCS1
Controller Options
B(1)
Not used
B(2)
Not used
B(3)
Not used
B(4)
Not used
B(5)
Not used
B(6)
Not used
B(7)
Not used
B(8)
Default Action 1=Reverse
136
Word
R/W
HDW1
Hardware Configuration
137
FP
R/W
HRI1
High Range AI1