FieldServer Metasys N2 FS-8700-19 User Manual
Page 41
FS-8700-19_Metasys_N2 Driver Manual
Page 41 of 51
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]
General dynamic Parameters
Relative Item Signal Condition Read/Write Johnson Tag Description
B(4)
DO6
TRIAC 6 ON
B(5)
DO7
TRIAC 7 ON
B(6)
DO1
TRIAC 1 ON
B(7)
DO2
TRIAC 2 ON
B(8)
Not used
32
Byte
Read
ROS
TC9100 Operation Status
B(1)
MODS
00 = Night mode
01 = Stand-by mode
10 = Comfort mode
B(2)
11 = OFF mode
B(3)
MODT
Temporary mode
B(4)
MODA
Alternate mode
B(5)
Supervisory mode enabled
B(6)
WIN
Window open
B(7)
OCC
Occupancy Sense
B(8)
AIRQ
Air Quality Sense
33
Byte
Write
MSK
Outputs Central Control - Enable
B(1)
DO3E
Enable TRIAC 3
B(2)
DO4E
Enable TRIAC 4
B(3)
DO5E
Enable TRIAC 5
B(4)
DO6E
Enable TRIAC 6
B(5)
DO7E
Enable TRIAC 7
B(6)
DO1E
Enable TRIAC 1
B(7)
DO2E
Enable TRIAC 2
34
Byte
Write
ODC
Outputs Central Control - Set Level
B(1)
DO3C
TRIAC 3 ON
B(2)
DO4C
TRIAC 4 ON
B(3)
DO5C
TRIAC 5 ON
B(4)
DO6C
TRIAC 6 ON
B(5)
DO7C
TRIAC 7 ON
B(6)
DO1C
TRIAC 1 ON
B(7)
DO2C
TRIAC 2 ON
35
Byte
Write
HLD
Control Loops Hold
B(1)
Loop #1 Hold
B(2)
Loop #2 Hold
B(3)
Loop #3 Hold
B(4)
Loop #4 Hold
B(5)
Loop #5 Hold
B(6)
Loop #6 Hold
36
Byte
Write
HLD
Computer mode Control
B(1)
Loop #1 Hold WSP override
B(2)
Loop #2 Hold WSP override
B(3)
Loop #3 Hold WSP override
B(4)
Loop #4 Hold WSP override
B(5)
Loop #5 Hold WSP override
B(6)
Loop #6 Hold WSP override
37
Byte
Write
SUP
Supervisory Mode Control
B(1)
MODC
00 = Night mode request
01 = Stand-by mode request
10 = Comfort mode request
B(2)
11 = OFF mode request
B(3)
SOFF
Shut-Off mode request
B(4)
STUP
Start-Up mode request
B(5)
Not used
B(6)
Supervisory Mode Control
B(7)
MAN
Manual OP Mode