beautypg.com

Caution – Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 92

background image

5-45

In case of F14 set value : 3.
The output frequency is lowered by the control by
which the DC voltage of the main circuit is kept
constant from the regeneration energy, so that the
inverter may continue operation when momentary
power failure occurs.

The response is adjusted with U23 and U24 at this
time.

Calculate the integral gain using the following formula.

value

set

23"

U

"

2

gain

Integral

16

=

[ms]

PI

calculator

H15

Set value

DC voltage of the

main circuit

Output frequency

command

|f

|

I gain:U23

P gain:U24

|f

|

0

Output frequency

command

|f

**

|

Input phase loss protection

U48

This function selects operation of input phase loss or
power supply unbalance protection.

U 4 8

U S E R 4 8

Setting range : 0 to 2

Set value

Operation

0

Active (without reactor (ACR/DCR))

1

Active (with reactor (ACR/DCR))

2 Inactive

When "2" is set to U48, protection
operation of the inverter to input phase
loss or power supply voltage unbalance
does not work. If you use it as it is,
there is a possibility of damaging an
inverter.
Failure may result.

RS-485 protocol selection

U49

The protocol of RS-485 communication is changed.

U 4 9

U S E R 4 9

Set value : 0, 1

Set value

Operation

0 FGI-bus
1 Modbus-RTU

Instruction manual and specifications are prepared
about communicative details. Contact Fuji Electric.

Speed agreement /PG error(Detection width)

U56

Speed agreement /PG error (Detection timer)

U57

PG e rro r sele ction

U58

These functions are effective for the option card

( OPC-G11S-PG,-PG2,-PGA ).

Refer to each manual.

U 5 6

U

S

E

R 5 6

U 5 7

U

S

E

R 5 7

U 5 8

U

S

E

R 5 8

When function code F13 (electronic thermal)is set to 2,
both the type of the braking resistor and connection
circuit are set. Factory setting is set to nominal applied
resistor and the number of resistor is one. When the
power load capacities of resistor are increased, set the
factory setting properly

U 5 9

U S E R 5 9

Setting range : 0 to A8 (HEX)


Setting of ten’s digit ( type selection )

Set

value

Type braking resistor

Resistance

[Ω]

Capacity

[W]

Duty

cycle

[%ED]

0

Standard applied resistor

- -

1 DB0.75-2C

100 200

2 DB2.2-2C

40

400

3 DB3.7-2C

33

400

4 DB5.5-2C

20

800

5 DB7.5-2C

15

900

6 DB0.75-4C

200 200

7 DB2.2-4C

160 400

8 DB3.7-4C

130 400

9 DB5.5-4C

80

800

A DB7.5-4C

60

900

10%


Setting of unit’s digit (connection circuit selection)

Braking-resistor

Set val

ue

Use

number

Connection circuit

*1)

Duty

cycle

[%ED]

Synthetic

resistance

[Ω]

Power

consumption per

resistance

[comparatively]

0

1

DB

10% R

100%

1

2

DB

20% 2R

50%

2

2

DB

20% (1/2)R

50%

3

4

DB

40% R

25%

4

3

DB

30% 3R

33%

5

6

DB

50% (3/2)R

17%

6

9

DB

50% R

11%

7

4

DB

40% 4R

25%

8

8

DB

50% 2R

12.5%

1) It is limited by the %ED value of the braking transistor
inside the inverter.

Braking - resistor function select

[30HP or less is corresponded]

U59

CAUTION