2-3-3 Connecting the control terminals

Table 2-3-3 lists the functions of the control circuit terminals. A control circuit terminal should be connected
according to the setting of its functions.

Table 2-3-3

Terminal

Classification

symbol

Terminal name

Function

13 Potentiometer

power

supply

Used for +10V DC power supply for frequency setting POT (variable
resistor of 1 to 5kΩ)

12 Voltage

input

Frequency is set according to the analog input voltage supplied from

an external circuit.

- 0 to +10V DC/0 to 100%
- Reversible operation using positive and negative signals:0 to +/-

10V DC/0 to 100%

- Reverse operation: +10 to 0V DC/0 to 100%

The feedback signal for PID control is input.

The analog input value from the external circuit is used for torque

control. (P11S does not support this function.)

* Input resistance: 22kΩ

V2

Voltage input

Frequency is set according to the analog input voltage supplied from an
external circuit

- 0 to +10V DC/0 to 100%
- Reverse operation:+10 to 0V DC/0 to 100%

* It can be used only one terminal "V2" or "C1" alternatively
* Input resistance:22kΩ

C1 Current

input

Frequency is set according to the analog input current supplied from

an external circuit.

- 4 to 20mA DC/0 to 100%
- Reverse operation:20 to 4mA DC/0 to 100%

The feedback signal for PID control is input.

PTC thermistor input

* It can be used only one terminal "V2" or "C1" alternatively.
* Input resistance:250Ω

Analog input

11

Analog input common

Common terminal for analog input signals

FWD Forward

operation/stop

command

Used for forward operation (when FWD-CM is on) or deceleration and
stop (when FWD-CM is off)

REV Reverse

operation/stop

command

Used for reverse operation (when REV-CM is on) or deceleration and
stop (when REV-CM is off)

X1

Digital input 1

X2

Digital input 2

X3

Digital input 3

X4

Digital input 4

X5

Digital input 5

X6

Digital input 6

X7

Digital input 7

X8

Digital input 8

X9

Digital input 9

The coast-to-stop command, external alarm, alarm reset, multistep
frequency selection, and other functions (from an external circuit) can be
assigned to terminals X1 to X9. For details, see "Setting the Terminal
Functions E01 to E09" in Section 5.2, "Details of Each Function."

*

Item min.

typ.

max.

ON

level

2V - 2V

Operating voltage

OFF level

22V

24V

27V

Operating current at ON level

-

3.2mA

4.5mA

Allowable leakage current at OFF level

-

-

0.5mA

CM

Common terminal

Common terminal for Digital input and FMP terminals

P24

Control Unit power Supply

+24VDC power supply for control input. Maximum output current 100mA

Digital input

PLC

PLC signal power

Used to connect power supply for PLC output signals (rated voltage
24(22 to 27) V DC) at source logic operation.

Analog output

FMA
(11:
Common
terminal)

Analog monitor

Outputs monitor signal using analog DC voltage 0 to +10V DC.
The meaning of this signal is one of the following:
-Output frequency (before slip compensation) -Power consumption
-Output frequency (after slip compensation) -PID feedback value
-Output current -PG feedback value
-Output voltage -DC link circuit voltage
-Output torque -Universal AO
-Load factor
*Connectable impedance:5kΩ minimum