beautypg.com

4-7 data format specification – Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 120

background image

9-11

9-4-7 Data Format Specification

All data in the data field of communication frame shall be represented by a 16 bit length word.

15 14 13

12 11 10 9 8 7 6 5 4 3 2 1 0

16 bits binary data


Data format [1]

Unsigned Integer data (Positive): Min. unit 1

Example If F15 (Frequency limit, upper)= 60Hz
60 = 003C

H


Data format [2]

Integer data (Positive, negative): Min. unit 1

Example data = -20
-20 = FFEC

H


Data format [3]

Unsigned Decimal data (Positive): Min. unit 0.1

Example: If F17 (frequency gain setting signal) = 100.0%
100.0 X 10 = 1000 = 03E8

H


Data format [4]

Decimal data (Positive, negative): Min. unit 0.1

Example If: C31 (Analog input offset adjust, terminal12) = - 5.0%
- 5.0 X 10= - 50 = FFCE

H


Data format [5]

Unsigned Decimal data (Positive): Min. unit 0.01

Example: If C05 (multi-step frequency 1) = 50.25Hz
50.25 X 100 = 5025 = 13A1

H


Data format [6]

Decimal data (Positive, negative): Min. unit 0.01

Example: If M07 (actual torque value)= - 85.38%
- 85.38 X 100= - 8538=DEA6

H


Data format [7]

Unsigned Decimal data (Positive): Min. unit 0.001

Example: If o05 (follow - up side ASR 1 constant) = 0.105s
0.105 X 1000 = 105 = 0069

H


Data format [8]

Decimal data (Positive, negative): Min. unit 0.001

Example: Data = -1.234
- 1.234 X 1000 = - 1234 = FB2E

H


Data format [9]

Unsigned Integer data (Positive): Min. unit 2

Example If P01 (Motor 1 number of poles) =2pole
2 = 0002

H