5-2
E:Extension Terminal Functions
Factory setting
Func
No.
NAME
LCD Display
Setting range
Unit
Min.
Unit
-30HP 40HP-
Change
during op
User
Set value
Remark
E01 X1 terminal function
E01
X1 FUNC
0 to 35
-
-
0
NA
E02 X2 terminal function
E02
X2 FUNC
1 NA
E03 X3 terminal function
E03
X3 FUNC
2 NA
E04 X4 terminal function
E04
X4 FUNC
3 NA
E05 X5 terminal function
E05
X5 FUNC
4 NA
E06 X6 terminal function
E06
X6 FUNC
5 NA
E07 X7 terminal function
E07
X7 FUNC
6 NA
E08 X8 terminal function
E08
X8 FUNC
7 NA
E09 X9 terminal function
E09
X9 FUNC
8 NA
E10 Acceleration time 2
E10
ACC TIME2
s
0.01
6.00
20.00
A
E11 Deceleration time 2
E11
DEC TIME2
6.00 20.00 A
E12 Acceleration time 3
E12
ACC TIME3
6.00 20.00 A
E13 Deceleration time 3
E13
DEC TIME3
6.00 20.00 A
E14 Acceleration time 4
E14
ACC TIME4
6.00 20.00 A
E15 Deceleration time 4
E15
DEC TIME4
0.01 to 3600s
6.00 20.00 A
E16 Torque limiter 2
(Driving)
E16
DRV TRQ 2
G11S: 20 to 200%, 999
%
1
999
A
P11S: 20 to 150%, 999
E17 (Braking)
E17
BRK TRQ 2
G11S: 0%, 20 to 200%, 999
%
1
999
A
G11S: 0%, 20 to 150%, 999
E20 Y1 terminal function
E20
Y1 FUNC
0 to 37
-
-
0
NA
E21 Y2 terminal function
E21
Y2 FUNC
1 NA
E22 Y3 terminal function
E22
Y3 FUNC
2 NA
E23 Y4 terminal function
E23
Y4 FUNC
7 NA
E24 Y5A, Y5C terminal func.
E24
Y5 FUNC
10 NA
E25 Y5 RY operation mode
E25
Y5RY MODE
0,1
-
1
0
NA
E30 FAR
function
(Hysteresis)
E30
FAR HYSTR
0.0 to 10.0Hz
Hz
0.1
2.5
A
E31 FDT
function
(Level)
E31
FDT1 LEVEL
G11S: 0 to 400Hz
Hz
1
60
A
P11S: 0 to 120Hz
E32 signal
(Hysteresis)
E32
FDT1 HYSTR
0.0 to 30.0Hz
Hz
0.1
1.0
A
E33 OL1 function(Mode select)
E33
OL1 WARNING
0: Thermal calculation
-
-
0
A
1: Output current
E34 signal
(Level)
E34
OL1 LEVEL
G11S: 5 to 200%
A
0.01
Motor rated current
A
P11S: 5 to 150%
E35 (Timer)
E35
OL1 TIMER
0.0 to 60.0s
s
0.1
10.0
A
E36 FDT2
function
(Level)
E36
FDT2 LEVEL
G11S: 0 to 400Hz
Hz
1
60
A
P11S: 0 to 120Hz
E37 OL2
function
(Level)
E37
OL2 LEVEL
G11S: 5 to 200%
A
0.01
Motor rated current
A
G11S: 5 to 150%
E40 Display coefficient A
E40
COEF A
-999.00 to 999.00
-
0.01
0.01
A
E41 Display coefficient B
E41
COEF B
-999.00 to 999.00
-
0.01
0.00
A
E42 LED Display filter
E42
DISPLAY FL
0.0 to 5.0s
s
0.1
0.5
A
E43 LED
Monitor
(Function)
E43
LED MNTR
0 to 12
-
-
0
A
E44
(Display at STOP mode)
E44
LED MNTR2
0, 1
-
-
0
A
E45 LCD
Monitor
(Function)
E45
LCD MNTR
0, 1
- -
0
A
E46
(Language)
E46
LANGUAGE
0 to 5
-
-
1
A
E47
(Contrast)
E47
CONTRAST
0(soft) to 10(hard)
-
-
5
A
C:Control Functions of Frequency
Factory setting
Func
No.
NAME
LCD Display
Setting range
Unit
Min.
Unit
-30HP
40HP-
Change
during op
User
Set value
Remark
C01 Jump frequency
(Jump freq. 1)
C01
JUMP Hz 1
Hz
1
0
A
C02
(Jump freq. 2)
C02
JUMP Hz 2
0 A
C03
(Jump freq. 3)
C03
JUMP Hz 3
G11S: 0 to 400Hz
P11S: 0 to 120Hz
0 A
C04
(Hysteresis)
C04
JUMP HYSTR
0 to 30Hz
Hz
1
3
A
C05 Multistep frequency
(Freq. 1)
C05
MULTI Hz-1
Hz
0.01
0.00
A
C06 setting
(Freq. 2)
C06
MULTI Hz-2
0.00 A
C07
(Freq. 3)
C07
MULTI Hz-3
0.00 A
C08
(Freq. 4)
C08
MULTI Hz-4
0.00 A
C09
(Freq. 5)
C09
MULTI Hz-5
0.00 A
C10
(Freq. 6)
C10
MULTI Hz-6
0.00 A
C11
(Freq. 7)
C11
MULTI Hz-7
0.00 A
C12
(Freq. 8)
C12
MULTI Hz-8
0.00 A
C13
(Freq. 9)
C13
MULTI Hz-9
0.00 A
C14
(Freq. 10)
C14
MULTI Hz-10
0.00 A
C15
(Freq. 11)
C15
MULTI Hz-11
0.00 A
C16
(Freq. 12)
C16
MULTI Hz-12
0.00 A
C17
(Freq. 13)
C17
MULTI Hz-13
0.00 A
C18
(Freq. 14)
C18
MULTI Hz-14
0.00 A
C19
(Freq. 15)
C19
MULTI Hz-15
G11S: 0.00 to 400.00Hz
P11S: 0.00 to 120.00Hz
0.00 A