beautypg.com

Fuji Bikes FRENIC 5000G11S/P11S User Manual

Page 119

background image

9-10

Monitoring parameter registers

Address Code

Description

Unit

Range

Min.

unit

Read/

Write

Data

Format

2049 M01

Frequency

command

(final command)

-

- 20000

–20000

(max. frequency at

± 20000)

1 R

[2]

2053 M05

Frequency

command

(final command)

Hz

0.00

–400.00

(P11S:0.00-120.00)

0.01 R [5]

2054 M06

Actual

frequency

-

- 20000

–20000

(max. frequency at

± 20000)

1 R

[2]

2055

M07

Actual torque value

%

- 200.00

–200.00

0.01 R [6]

2056 M08

Torque

current

%

- 200.00

–200.00

0.01 R [6]

2057 M09

Output

frequency

Hz

0.00

–400.00

(P11S:0.00-120.00)

0.01 R [5]

2058

M10

Motor output (input
electric power)

%

0.00

–200.00

0.01 R [5]

2059

M11

Output current r. m. s.

%

0.00

–200.00 (inverter rating

at 100.00)

0.01 R [5]

2060

M12

Output voltage r. m. s.

V

0.0

–600.0

1.0 R [3]

2061

M13

Operation command (final
command)

-

Refer to data format [14]

-

R

[14]

2062 M14

Operating

state

-

Refer

to data format [16]

-

R

[16]

2063

M15

Universal output terminal
data

-

Refer to data format [15]

-

R

[15]

2064 M16

Fault

memory

0

2065 M17

Fault

memory

1

2066 M18

Fault

memory

2

2067 M19

Fault

memory

3

-

Refer to data format [10]

-

R

[10]

2068 M20

Integrated

operating

time

h

0

–65535

1 R

[1]

2069

M21

DC link voltage

V

0

–1000

1 R

[1]

2071

M23

Type code

-

Refer to data format [17]

-

R

[17]

2072

M24

Inverter capacity code

-

Refer to data format [11]

-

R

[11]

2073 M25

ROM

version

-

0

–64999

1 R

[1]

2074 M26

Transmission

error

processing code

-

Refer to data format [20]

-

R

[20]

2075

M27

Frequency command at
alarm (final command)

-

- 20000

–20000 (max.

frequency at

±20000 )

1 R

[2]

2079

M31

Frequency command at
alarm (final command)

Hz

0.00

–400.00

(P11S:0.00-120.00)

0.01 R [5]

2080

M32

Actual frequency at alarm

-

- 20000

–20000

(max. frequency at

± 20000)

1 R

[2]

2081

M33

Actual torque at alarm

%

- 200.00

– 200.00

0.01 R [6]

2082

M34

Torque current at alarm

%

- 200.00

– 200.00

0.01 R [6]

2083

M35

Output frequency at alarm

Hz

0.00

– 400.00

(P11S:0.00-120.00)

0.01 R [5]

2084

M36

Motor output at alarm
(input power)

%

0.00

–200.00

0.01 R [5]

2085

M37

Output current r.m.s. at
alarm

%

0.00

– 200.00 (inverter rating

at 100.00)

0.01 R [5]

2086

M38

Output voltage effective
value at alarm

V

0.0

– 600.0

1.0 R [3]

2087

M39

Operation command at
alarm

-

Refer to data format [14]

-

R

[14]

2088

M40

Operating state at alarm

-

Refer to data format [16]

-

R

[16]

2089

M41

Universal output terminal
data at alarm

-

Refer to data format [15]

-

R

[15]

2090 M42

Integrated

operation

time

at alarm

h

0

–65535

1 R

[1]

2091

M43

DC link voltage at alarm

V

0

–1000

1 R

[1]

2092

M44

Inverter internal air
temp.at alarm

°C

0

–120

1 R

[1]

2093

M45

Cooling fin temp. at alarm

°C

0

–120

1 R

[1]

2094

M46

Life of main circuit
capacitor.

%

0.0

–100.0

0.1 R [3]

2095

M47

Life of printed circuit
board capacitor.

h

0

–65535

1 R

[1]

2096

M48

Life of cooling fan.

h

0

–65535

1 R

[1]