Monitoring parameter registers
Address Code
Description
Unit
Range
Min.
unit
Read/
Write
Data
Format
2049 M01
Frequency
command
(final command)
-
- 20000
–20000
(max. frequency at
± 20000)
1 R
[2]
2053 M05
Frequency
command
(final command)
Hz
0.00
–400.00
(P11S:0.00-120.00)
0.01 R [5]
2054 M06
Actual
frequency
-
- 20000
–20000
(max. frequency at
± 20000)
1 R
[2]
2055
M07
Actual torque value
%
- 200.00
–200.00
0.01 R [6]
2056 M08
Torque
current
%
- 200.00
–200.00
0.01 R [6]
2057 M09
Output
frequency
Hz
0.00
–400.00
(P11S:0.00-120.00)
0.01 R [5]
2058
M10
Motor output (input
electric power)
%
0.00
–200.00
0.01 R [5]
2059
M11
Output current r. m. s.
%
0.00
–200.00 (inverter rating
at 100.00)
0.01 R [5]
2060
M12
Output voltage r. m. s.
V
0.0
–600.0
1.0 R [3]
2061
M13
Operation command (final
command)
-
Refer to data format [14]
-
R
[14]
2062 M14
Operating
state
-
Refer
to data format [16]
-
R
[16]
2063
M15
Universal output terminal
data
-
Refer to data format [15]
-
R
[15]
2064 M16
Fault
memory
0
2065 M17
Fault
memory
1
2066 M18
Fault
memory
2
2067 M19
Fault
memory
3
-
Refer to data format [10]
-
R
[10]
2068 M20
Integrated
operating
time
h
0
–65535
1 R
[1]
2069
M21
DC link voltage
V
0
–1000
1 R
[1]
2071
M23
Type code
-
Refer to data format [17]
-
R
[17]
2072
M24
Inverter capacity code
-
Refer to data format [11]
-
R
[11]
2073 M25
ROM
version
-
0
–64999
1 R
[1]
2074 M26
Transmission
error
processing code
-
Refer to data format [20]
-
R
[20]
2075
M27
Frequency command at
alarm (final command)
-
- 20000
–20000 (max.
frequency at
±20000 )
1 R
[2]
2079
M31
Frequency command at
alarm (final command)
Hz
0.00
–400.00
(P11S:0.00-120.00)
0.01 R [5]
2080
M32
Actual frequency at alarm
-
- 20000
–20000
(max. frequency at
± 20000)
1 R
[2]
2081
M33
Actual torque at alarm
%
- 200.00
– 200.00
0.01 R [6]
2082
M34
Torque current at alarm
%
- 200.00
– 200.00
0.01 R [6]
2083
M35
Output frequency at alarm
Hz
0.00
– 400.00
(P11S:0.00-120.00)
0.01 R [5]
2084
M36
Motor output at alarm
(input power)
%
0.00
–200.00
0.01 R [5]
2085
M37
Output current r.m.s. at
alarm
%
0.00
– 200.00 (inverter rating
at 100.00)
0.01 R [5]
2086
M38
Output voltage effective
value at alarm
V
0.0
– 600.0
1.0 R [3]
2087
M39
Operation command at
alarm
-
Refer to data format [14]
-
R
[14]
2088
M40
Operating state at alarm
-
Refer to data format [16]
-
R
[16]
2089
M41
Universal output terminal
data at alarm
-
Refer to data format [15]
-
R
[15]
2090 M42
Integrated
operation
time
at alarm
h
0
–65535
1 R
[1]
2091
M43
DC link voltage at alarm
V
0
–1000
1 R
[1]
2092
M44
Inverter internal air
temp.at alarm
°C
0
–120
1 R
[1]
2093
M45
Cooling fin temp. at alarm
°C
0
–120
1 R
[1]
2094
M46
Life of main circuit
capacitor.
%
0.0
–100.0
0.1 R [3]
2095
M47
Life of printed circuit
board capacitor.
h
0
–65535
1 R
[1]
2096
M48
Life of cooling fan.
h
0
–65535
1 R
[1]