9-4-5 Inverter Function Code Access

All of the inverter function codes are accessible through the RS-485 serial interface. Inverter function codes
are mapped to RTU holding registers. An inverter function code RTU address is 2 bytes in length. The high
byte corresponds to a code that represents the inverter parameter sort (F

–M). The low byte corresponds to

the inverter parameter number within the sort (0 -99).

Code Sort

Name

Code

Sort

Name

0

F

Basic function

5

A

Motor 2 function

1 E Terminal

function 6 o Option

function

2 C Control

function 7 S Command/function

data

3

P

Motor 1 function

8

M

Monitor data

4

H

High level function

For example, inverter function code M11, output current, is addressed as RTU parameter number 080B
hexadecimal or 2059 decimal.

9-4-6 Command and Monitor Data Registers

The command and monitor function codes are used to control the operation of the inverter and monitor the
status variables through the serial interface. The command and monitor function codes are not accessible
from the inverter keypad interface. Inverter parameter H30 and digital input signal LE must be enabled to
operate the inverter from the Modbus interface. If LE is not assigned to a digital input (X1-X9), the signal will
default to ON.


Frequency Setting Registers

Address Code

Name

Unit

Variable Range

Min. unit

Read/

Write

Data

Format

1793 S01

Frequency

command -

-20000

–20000

(max. frequency at

± 20000)

1

R/W

2

1797 S05

Frequency

command Hz

0.00

–400.00 0.01

R/W

5

Note:
1) If both S01 and S05 are set, the inverter will ignore the setting of S05.
2) A data setting that exceeds the setting range is possible, but the actual action will be limited by the inverter
configuration.


Operation command data Registers

Address Code

Name

Unit

Variable Range

Min. unit

Read/

Write

Data

Format

1798

S06

Operation command

-

Refer to the data format [14]

-

R/W

14

1799

S07

Universal Do

-

Refer to the data format [15]

-

R/W

15

1804 S12

Universal

Ao

-

-20000

–20000

(100% output at

± 20000 )

1 R/W 2

Note:
1) Since X1

–X9 are configurable input commands, it is necessary to set the functions by E01–E09.

2) The alarm reset is executed, when RST signal changes from ON to OFF even if there are no alarms.
3) Universal Do is a function that utilizes the inverter

’s digital outputs via communication.


Function data Registers

Address Code

Name

Unit

Variable Range

Min. unit

Read/

Write

Data

Format

1800

S08

Acceleration time F07

s

0.1

–3600.0

0.1 R/W 3

1801

S09

Deceleration time F08

s

0.1

–3600.0

0.1 R/W 3

1802

S10

Torque limit level 1
(driving) F40

%

20.00

–200.00, 999

(P11S:20.00-150.00)

1.00 R/W 5

1803

S11

Torque limit level 2
(braking) F41

%

0.00, 20.00

–200.00, 999

(P11S:20.00-150.00)

1.00 R/W 5

Note:
1) The writing of data out of range is treated as out of range error.
2) Use a value of 7FFF

H

to enter 999 for torque limit functions.

high byte

low byte

inverter parameter sort code

inverter parameter number