P:motor parameters, H:high performance functions – Fuji Bikes FRENIC 5000G11S/P11S User Manual
Page 50
5-3
Factory setting
Func
No.
NAME
LCD Display
Setting range
Unit
Min.
Unit
-30HP 40HP-
Change
during op
User
Set value
Remark
C20 JOG
frequency
C20
JOG Hz
G11S:0.00 to 400.00Hz
Hz
0.01
5.00
A
P11S:0.00 to 120.00Hz
C21 PATTERN(Mode
select)
C21
PATTERN 0,1,2
-
-
0
NA
operation
C22 (Stage
1)
C22
STAGE 1
Operation time:0.00 to 6000s
s
0.01
0.00 F1
A
C23 (Stage
2)
C23
STAGE 2
F1 to F4 and R1 to R4
0.00 F1
A
C24 (Stage
3)
C24
STAGE 3
0.00 F1
A
C25 (Stage
4)
C25
STAGE 4
0.00 F1
A
C26 (Stage
5)
C26
STAGE 5
0.00 F1
A
C27 (Stage
6)
C27
STAGE 6
0.00 F1
A
C28 (Stage
7)
C28
STAGE 7
0.00 F1
A
C30 Frequency command 2
C30
FREQ CMD 2
0 to 11 -
-
2
NA
C31 Offset
adjust(terminal[12])
C31
BIAS 12
-100.0 to +100.0%
%
0.1
0.0
A
C32
C32
GAIN 12
0.0 to +200.0%
%
0.1
100.0
A
C33 Analog setting signal filter
C33
REF FILTER
0.00 to 5.00s
s
0.01
0.05
A
P:Motor Parameters
P01 Number of motor 1 poles
P01
M1 POLES
2 to 14
-
2
4
NA
P02 Motor
1
(Capacity)
P02
M1-CAP
Up to 30[HP]: 0.01 to 60HP
HP
0.01
Motor Capacity
NA
40[HP]and above: 0.01 to 800HP
P03
(Rated current)
P03
M1-Ir
0.00 to 2000A
A
0.01
Motor rated current
NA
P04
(Tuning)
P04
M1 TUN1
0, 1, 2
-
-
0
NA
P05
(On-line Tuning)
P05
M1 TUN2
0, 1
-
-
0
NA
P06
(No-load current)
P06
M1-Io
0.00 to 2000A
A
0.01
NA
Fuji STANDARD RATED
VALUE
P07
(%R1
setting)
P07
M1-%R1
0.00 to 50.00%
%
0.01
A
Fuji STANDARD RATED
VALUE
P08 (%X
setting)
P08
M1-%X
0.00 to 50.00%
%
0.01
A
Fuji STANDARD RATED
VALUE
P09 Slip compensation control 1
P09
SLIP COMP1
0.00 to 15.00Hz
Hz
0.01
0.00
A
H:High Performance Functions
H03 Data
initializing
H03
DATA INIT
0, 1
-
-
0
NA
H04 Auto-reset
(Times)
H04
AUTO-RESET
0, 1 to 10 times
-
1
0
A
H05 (Reset
interval)
H05
RESET INT
2 to 20s
s
1
5
A
H06 Fan stop operation
H06
FAN STOP
0, 1
-
-
0
A
H07 ACC/DEC
pattern
(Mode select)
H07
ACC PTN
0,1,2,3
-
-
0
NA
H08 Rev. phase sequence lock
H08
REV LOCK
0, 1
-
-
0
NA
H09 Start
mode
H09
START MODE
0, 1, 2
-
-
0
NA
H10 Energy-saving
operation
H10
ENERGY SAV
0, 1
-
-
G11S:0
A
P11S:1
H11 DEC
mode
H11
DEC MODE
0, 1
-
-
0
A
H12 Instantaneous OC limiting
H12
INST CL
0, 1
-
-
1
NA
H13 Auto-restart
(Restart time)
H13
RESTART t
0.1 to 10.0s
s
0.1
0.1
NA
H14
(Freq. fall rate)
H14
FALL RATE
0.00 to 100.00Hz/s
Hz/s
0.01
10.00
A
H15
(Holding DC voltage)
H15
HOLD V
3ph 230V class: 200 to 300V
V
1
230V class:235V
A
3ph 460V class: 400 to 600V
460V class:470V
H16
(OPR command selfhold time)
H16
SELFHOLD t
0.0 to 30.0s, 999
s
0.1
999
NA
H18 Torque
control
H18
TRQ CTRL
G11:0, 1, 2, P11:0
-
-
0
NA
H19 Active
drive
H19
AUT RED
0, 1
-
-
0
A
H20 PID
control
(Mode select)
H20
PID MODE
0, 1, 2
-
-
0
NA
H21
(Feedback signal)
H21
FB SIGNAL
0, 1, 2, 3
-
-
1
NA
H22 (P-gain)
H22
P-GAIN
0.01 to 10.00 times
-
0.01
0.1
A
H23
(I-gain)
H23
I-GAIN
0.0 , 0.1 to 3600s
s
0.1
0.0
A
H24 (D-gain)
H24
D-GAIN
0.00s , 0.01 to 10.0s
s
0.01
0.00
A
H25 (Feedback
filter)
H25
FB FILTER
0.0 to 60.0s
s
0.1
0.5
A
H26 PTC
thermistor
(Mode select)
H26
PTC MODE
0, 1
0 A
H27 (Level)
H27
PTC LEVEL
0.00 to 5.00V
V
0.01
1.60
A
H28 Droop
operation
H28
DROOP
G11:-9.9 to 0.0Hz, P11:0.0 (Fixed.)
Hz
0.1
0.0
A
H30 Serial link
(Function select)
H30
LINK FUNC
0, 1, 2, 3
-
-
0
A
H31 Modbus-RTU
(Address)
H31
ADDRESS
0 (broadcast), 1 to 247
-
1
1
NA
H32
(Mode select on no response error)
H32
MODE ON ER
0, 1, 2, 3
-
-
0
A
H33
(Timer)
H33
TIMER
0.0 to 60.0s
s
0.1
2.0
A
H34
(Baud
rate)
H34
BAUD RATE
0, 1, 2, 3
-
-
1
A
H35
(Data
length)
H35
LENGTH
0 (8-bit fixed)
-
-
0
A
H36
(Parity
check)
H36
PARITY
0, 1, 2
-
-
0
A
H37
(Stop
bits)
H37
STOP BITS
0(2bit), 1(1bit)
-
-
0
A
H38
(No response error detection time)
H38
NO RES t
0 (No detection), 1 to 60s
s
1
0
A
H39 (Response
interval)
H39
INTERVAL
0.00 to 1.00s
s
0.01
0.01
A