C. The Command Interpreter (CI)

C-26

Festo P.BE-MTR-DCI-DN-EN en 1209a

C.2.5

Standardised Device Profile Area (6xxxh)

Control word

CI

6040h

00h

Var

uint16

rw

Description

For modifying the current controller status or triggering an action. Status
changes triggered by the control word must be read back via the status word.
Only after the requested status has been read from the status word may a
further command be written via the control word.
For values see Tab. C/8

Bit

Value

Description

0

0x0001

Switch on

Controlling the state transitions.
These bits are evaluated together!

1

0x0002

Enable Voltage

2

0x0004

Quick Stop – low-active!

3

0x0008

Enable Operation

4

0x0010

Mode-specific (object 6060h):

Homing mode:

Homing Operation Start

Profile Position Mode / Torque Mode: New Setpoint (move to position)

5

0x0020

Mode-specific (object 6060h):

Homing Mode:

reserved (set to 0)

Profile Position Mode: reserved (change_set_immediately in record

selection and direct mode is not supported)

Profile Torque Mode:

=1: With stroke limitation; =0: Without stroke

limitation

6

0x0040

Mode-specific (object 6060h):

Profile Position Mode: absolute / relative

Homing Mode:

reserved (set to 0)

Profile Torque Mode:

reserved (set to 1)

7

0x0080

Fault Reset

8

0x0100

Halt as per Halt Option Code – object 605Dh.

9

0x0200

Reserved (= 0)

10

0x0400

Reserved (= 0)

11

0x0800

Jog positive: Move while set (as with FHPP CPOS.B3)

12

0x1000

Jog negative: Move while set (as with FHPP CPOS.B4)

13

0x2000

Teach: Apply current value

14

0x4000

Reserved (= 0)

15

0x8000

Reserved (= 0)

Tab. C/8: Description of Control Word