beautypg.com

Commissioning 5-43 – Festo Электромотор MTR-DCI User Manual

Page 141

background image

5. Commissioning

5-43

Festo P.BE-MTR-DCI-DN-EN en 1209a

1. Record selection: establish “ready to operate”
status

1.1

Basic status of the drive when the supply voltage is
switched on.
} Step 1.2 or 1.3

1.2

Disable device control by FCT/HMI.
Optionally, the takeover of device control by FCT/HMI
can be blocked with CCON.B5 = 1 (LOCK).
} Step 1.3

1.3

Enable drive (record selection)
} Homing: example 4, Tab. 5/12.

Step/
Description

O data

I data

Byte

B7 B6 B5 B4 B3 B2 B1 B0 Byte

B7 B6 B5 B4 B3 B2 B1 B0

1.1 Basic status

(HMI device control =
off )

Byte 1

OPM2 OPM1

LOCK

RESET BRAKE STOP

ENABL

Byte 1

OPM2 OPM1 LOCK

24VL

FAULT WARN OPEN ENABL

CCON

0

0

0

0

0

x

0

0

SCON

0

0

0

1

0

0

0

0

Byte 2

CLEAR TEACH JOGN

JOGP

HOM

START

HALT

Byte 2

REF

STILL

DEV

MOV TEACH

MC

ACK

HALT

CPOS

0

0

0

0

0

0

0

0

SPOS

0

0

0

0

0

1

0

0

1.2 Disable device
control by FCT/HMI

Byte 1

OPM2 OPM1

LOCK

RESET BRAKE STOP

ENABL

Byte 1

OPM2 OPM1 LOCK

24VL

FAULT WARN OPEN ENABL

CCON

x

x

1

0

x

x

x

x

SCON

x

x

0

x

x

x

x

x

Byte 2

CLEAR TEACH JOGN

JOGP

HOM

START

HALT

Byte 2

REF

STILL

DEV

MOV TEACH

MC

ACK

HALT

CPOS

0

x

x

x

x

x

x

x

SPOS

x

x

x

x

x

x

x

x

1.3 Enable drive,
enable operation

(Record Select)

Byte 1

OPM2 OPM1

LOCK

RESET BRAKE STOP

ENABL

Byte 1

OPM2 OPM1 LOCK

24VL

FAULT WARN OPEN ENABL

CCON

0

0

x

0

0

x

1

1

SCON

0

0

0

1

0

0

1

1

Byte 2

CLEAR TEACH JOGN

JOGP

HOM

START

HALT

Byte 2

REF

STILL

DEV

MOV TEACH

MC

ACK

HALT

CPOS

0

0

0

0

0

0

0

1

SPOS

0

0

0

0

0

1

0

1

0: 0 signal

1: 1 signal;

x: not relevant (any);

F: Edge positive

Tab. 5/9: I/O data “Record selection: establish ready to operate status”

If there are faults after switching on or after setting CCON.B0
(ENABLE):
} Fault handling: see example 3, Tab. 5/11.