7 examples of i/o data, Ensuring device control, Commissioning 5-42 – Festo Электромотор MTR-DCI User Manual

Page 140: Step/ description o data i data

background image

5. Commissioning

5-42

Festo P.BE-MTR-DCI-DN-EN en 1209a

5.5.7

Examples of I/O data

The following pages provide typical examples of the I/O data
according to the FHPP standard:

1. Record selection: establish “ready to operate” status

2. Direct task: establish “ready to operate” status

3. Fault handling

4. Homing

5. Record selection: Positioning mode

6. Direct task: Positioning mode

7. Direct task: Force mode

A description of the MTR-DCI's finite state machine can be
found in section 5.8.

Ensuring device control

Step/
Description

O data

I data

Byte

B7 B6 B5 B4 B3 B2 B1 B0 Byte

B7 B6 B5 B4 B3 B2 B1 B0

0.1 HMI device con-
trol = on

Byte 1

OPM2 OPM1

LOCK

RESET BRAKE STOP ENABL

Byte 1

OPM2 OPM1 LOCK

24VL

FAULT WARN OPEN ENABL

CCON

0

0

0

0

0

x

0

0

SCON

0

0

1

1

0

0

0

0

Byte 2

CLEAR TEACH JOGN

JOGP

HOM

START

HALT

Byte 2

REF

STILL

DEV

MOV TEACH

MC

ACK

HALT

CPOS

0

0

0

0

0

0

0

0

SPOS

0

0

0

0

0

1

0

0

0: 0 signal

1: 1 signal;

x: not relevant (any);

F: Edge positive

Tab. 5/8: I/O data: “Device control active”

Device control via the control panel or the Festo Configuration
Tool has been activated. To control the MTR-DCI via the
DeviceNet interface, device control by FCT/HMI must first
be deactivated.