Table 11-3 modbus local slave functions - response – Lantronix XPORT PROTM 900-560 User Manual
Page 99

11: Modbus
XPort Pro User Guide
99
Table 11-3
Modbus Local Slave Functions - Response
Force Single Coil
0x05
0x00
0x00-0x02
Output CP
CP1 – CP3
0xff (set CPx 
to 1) or
0x00 (set CPx 
to 0)
0x00
N/A
N/A
Preset Single 
Register
0x06
0x00
0x00-0x02
CP1 – CP3
0x00
0x00 or 0x01
N/A
N/A
Force Multiple 
Coils
0x0F
0x00
0x00-0x02
Starting CP
CP1 – CP3
0x00
0x01-0x03
No of CPs to 
set
0x01
0B00000xyz
CP values ,Lo 
CP# in low bit
Preset Multiple 
Registers
0x10
0x00
0x00-0x02
Starting CP
CP1 – CP3
0x00
0x01-0x03
No of CPs to 
set
0x02-0x06
(No of CPs 
to set) * 2
Max [6]..
0x00, 0x0Y
0x00 ,0x0Y
0x00, 0x0Y
Y = 0 or 1
Read/Write 4X 
Registers
0x17
0x00
0x00-0x02
Starting CP
CP1 – CP3 to 
read
0x00
0x01-0x03
Quantity to 
read
0x00
0x00-0x02
Starting CP
CP1 – CP3 to 
write
0x00
0x01-0x03
Quantity to 
write
0x02-0x06
(Quantity to 
write) * 2
Max [6]..
0x00, 0x0Y
0x00 ,0x0Y
0x00, 0x0Y
Y = 0 or 1
Name
Number
Byte 
Count
Data [0]
Data [1]
Data 
[2]
Data [3]
Data
[4]
Data [5]
Read 
Coils
0x01
0x01
0B00000xyz
CP output 
values ,Lo CP# 
in high bit
N/A
N/A
N/A
N/A
N/A
Read 
Input 
status
0x02
0x01
0B00000xyz
CP output 
values ,Lo CP# 
in high bit
N/A
N/A
N/A
N/A
N/A
Read 
Holding 
Registers
0x03
0x02-0x06
0x00
Starting CP 
Value
0x00 or 0x01
0x00
Next CP or 
End CP value
0x00 or 0x01
0x00
End CP value
0x00 or 0x01
Read 
Input 
Registers
0x04
0x02-0x06
0x00
Starting CP 
Value
0x00 or 0x01
0x00
Next CP or 
End CP value
0x00 or 0x01
0x00
End CP value
0x00 or 0x01
Force 
Single 
Cell
0x05
Echo query
Echo query
Echo query
Echo 
query
N/A
N/A
N/A
Preset 
Single 
Register
0x06
Echo query
Echo query
Echo query
Echo 
query
N/A
N/A
N/A
Name
Number
Address 
Hi [0]
Address
Lo [1]
Data Hi
[2]
Data Lo
[3]
Bytes 
Count [4]
Value [5]