Heat & Glo • 6000TRS-CE • 2049-900 Rev. R • 3/13

22

Figure 17. Installing Support Brackets

3. Install Firestops

For Horizontal Runs - Firestops are REQUIRED on

both sides of a combustible wall through which the

flue passes.
To install firestops (heat shield) for horizontal runs that

pass through either interior or exterior walls:
• Cut a 25,4 cm X 30,5 cm hole through the wall.
• Position the firestops on both sides of the hole

previously cut and secure the firestops with nails or

screws.

• The pipe opening of the firestops

MUST BE placed

towards the bottom of the firestop.

• Continue the flue run through the firestop.

WALL BRACKET

WALL STUD

FLUE

OUTLET

2,5 cm

MINIMUM

2,4 m

For vertical Runs - The flue system must be

supported every 240 cm above the heater flue outlet

by wall brackets.
To install support brackets for vertical runs:
• Attach wall brackets to the flue pipe and secure the

wall bracket to the framing members with nails or

screws.