ProSoft Technology PS-QS-1x10-0781 User Manual
Page 86

FieldServer Configuration Manual
Page 86 of 90
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: [email protected]
Error
Description
Action
10126
The BACNet driver received a request for a
read_property_multiple with multiple objects.
This is not reported in the current release of the
BACNet driver.
10127
An UDP socket buffer overflowed and UDP
data was lost.
10128
The keyword MY_IP has been used in the
FS_TCP.INI file.
Only use KW_N1 and KW_N2
10129
The keyword N1_IP has been used in the
SMCTCP.INI file.
Use the FS_TCP.INI file.
10130
UDP broadcast panics has been disabled until
a hardwired send is added
10133
The ARP resolve queue has been overrun. This
is typically the result of a mis-configuration on
the FieldServer.
Check all IP_addresses, in particular the gateway
address.
10134 A cache block was not created
The Client side plc_channel has not yet been
discovered, or an attempt to write to an Analog_Input
Data_Type
10136
A temporary write block has been removed
because an identical one existed. Write data
might have been lost.
10209
Warning: the Server is responding with data
from an explicit Map Descriptor that is not
reading continuously
10210
Info: the inet Server received a write to input
command that is not supported.
10214
Warning: A Server side driver tried to read
from a Data_Object that has a WRBX as a
responsible Map Descriptor. The data being
read from the Server side might not be the
same as on the Client side.
10216
A Server node is associated with more than
one Client Node.
10302
An IP Fragmented packet was received while
IP Defragmentation was disabled.
Display "RX IP fragments" stat in the Ethernet api stat
screen. If this occurs frequently enable IP
Defragmentation
10401 The I/Net Server ignored a write to an Input
10402
The Baud Rate on a Connections Port has not
been defined.
A default value will be used.
10403
The MSTP driver must run at a cycle time
shorter that 10ms or proper operation cannot
be guaranteed
10404
The Write Queue is full and data has been
overwritten. This could be caused by using
moves to do multiple write-thru’s on a RDBC
Map Descriptor.
Solve by increasing the Write_Queue_Size or slowing
write-thru’s.