6.1.4 Node_Online_Bits
This Data Array function allows the user to specify Nodes and Subnets for which communication status is required.
Example:
Typical Data Array Parameters are:
Section Title
Data_Arrays
Column Title
Function
Legal Values
Data_Array_Name
Provide name for Data Array
Up
to
15
alphanumeric
characters
Data_Format
Provides Data format
Bit
Data_Array_Length
If specified, this allows the user to configure the number
subsequent nodes after the Node_ID.
1 to 256
Data_Array_Function Special function for Data Array
Node_Online_Bits,
None
Node_ID*
If configured, the Node address of the specified Node will be at
offset 0. The length parameter will be used to determine the
number of Node addresses starting from the Node_ID. If not
declared or specified as -, Node_ID 0 will be at offset 0.
1 to 256, -
Subnet_ID*
This allows the subnet of the Node to be declared. If subnets
are not used, this parameter can be excluded. If specified as -,
the subnet is ignored and all Nodes will be found.
0 to 256, -
Data_Arrays
Data_Array_Name , Data_Format , Data_Array_Length , Data_Array_Function , Node_ID , Subnet_ID
Node_on_Net
, Bit
, 30
, Node_Online_Bits
, 1
, -
Node_on_Net1
, Bit
, 30
, Node_Online_Bits
, 1
, 1
Node_on_Net2
, Bit
, 30
, Node_Online_Bits
, 10
, 2
Node_on_Net3
, Bit
, 30
, Node_Online_Bits
, 10
, 3
Node_on_Net4
, Bit
, 30
, Node_Online_Bits
, 10
, 4
Node_on_Net5
, Bit
, 30
, Node_Online_Bits
, 10
, 5