Error

Description

Action

failed because the Node did not have a
connection

write to this Node occurred before the Server_Name
mechanism discovered a valid connection.

10103

The maximum number of concurrent cache
blocks has been exceeded. A write
cache_block poll did not occur

10104

Connection mode of Hot_Standby_Data is only
supported in Hot Standby Mode1

10105

PLC_Port_Count = 1 only supported in
hot_standby mode2.

Set FieldServer parameter hs_mode to mode2

10106

An invalid hot_standby_mode has been
specified

as

part

of

the

FieldServer

parameters,

check hsb_p(s).ini files

10107

Could not create cache block - possibly
because the maximum number of data_points
has been exceeded

Contact FST.

10108

A BACNet alarm event was generated but the
required Alarm Limits has not been set

10110

Hot_Standby "partner_discover" found a
PRIMARY SECONDARY mismatch

10111

Hot_Standby "partner_discover" found an API
Version mismatch

10112

Hot_Standby "partner_discover" found a DCC
version mismatch

10113

Hot_Standby "partner_discover" found a
config file mismatch

10114

A Node_ID > 255 was used in the Hot_Standby
commbit configuration.

10116

A port other than P1/R1 was specified on an
X20. The port handle has been changed to
point to the only UART on X20.

10117

The Gateway Address for adapter N1 has not
been specified. This FieldServer will only be
accessible on the local TCP/IP subnet.

10118

The NETMASK for adapter N1 or N2 has not
been specified. This FieldServer will not be
accessible on the TCP/IP network through one
or both of these adapters.

10119

The IP_ADDRESS for adapter N1 or N2 has not
been specified. This FieldServer will not be
accessible on the TCP/IP network through one
or both of these adapters.

10120 An unrecognized rui_command was received.

Check that the Ruinet and Kernel versions match.

10125

In the BACNet driver, the OPTION_LIST
specified caused the packet buffer to be
exceeded. As a result the packet buffer was
truncated.