ProSoft Technology PS-QS-1x10-0781 User Manual
Page 12

FieldServer Configuration Manual
Page 12 of 90
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: [email protected]
/==========================================================
//
// Server Side Connections
//
Connections
Adapter
, Protocol
N1
, Modbus/TCP
//==========================================================
//
// Server Side Nodes
//
Nodes
Node_Name , Node_ID , Protocol
MBP_Srv_11 , 11
, Modbus/TCP
//==============================================================
//
// Server Side Map Descriptors
//
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Address , Length
SMD_DI_01
, DA_DI_01
, 0
, Passive
, MBP_Srv_11 , 10001
, 200
SMD_DO_01
, DA_DO_01
, 0
, Passive
, MBP_Srv_11 , 00001
, 200
Adapter definition applies to defining network
and FieldServer (e.g. Profibus) connections.
A Node name for
reference by the
Map Descriptors.
Since the FieldServer is a Server here, this is the ID of the FieldServer (virtual)
Node. The FieldServer can represent multiple Virtual Node_ID’s in most protocols.
The protocol for the network
connected to this port.
Settings for how the FieldServer communicates with Client Nodes.