beautypg.com

ProSoft Technology PS-QS-1x10-0781 User Manual

Page 84

background image

FieldServer Configuration Manual

Page 84 of 90

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: [email protected]

Error

Description

Action

10049 Could not find Client Data Array for Move.
10050 Could not find Server Data Array for Move.
10051 Could not find Feedback Data Array for Move.
10052 Could not find Mode Data Array for Move.
10053 Data Array already has a responsible move

10054

Setpoint Moves are only allowed to be 1 item
in length.

10055

A move was defined, and a write occurred to
the target Data Array, but cannot transfer to
the Source Data Array because no Responsible
Active Map Descriptor is defined.

10056

A move was defined, and a write occurred to
the target Data Array, but cannot transfer to
the Source Data Array because the Node
associated with the Responsible Active Map
Descriptor is offline.

10058

8051bp03 or CB8MENU found SMCTCP.INI and
FS_TCP.INI files, so it will delete FS_TCP.INI
and use SMCTCP.INI in future.

10059 Old version of RUIBOOT.EXE being used.

Obtain latest RUIBOOT or use manual method of
setting IP address - see Utilities manual.

10070 Illegal Node_ID.

10071 Map Descriptor length of 0 is not allowed.

10072 Map Descriptor length too large.

10073 Illegal Data Type for J-Bus.

Legal values = AI AR DI DR.

10074

An attempt to generate a write cache block
failed because the Node did not have a
connection.

10075 Illegal Map Descriptor address.

10076

This section of Data Array already has a
responsible Map Descriptor.

10077 Unable to add parameters from this line.

Ensure Map Descriptor headings are included in the
.CSV file.

10079

Map Descriptor length greater than Data Array
length

10082

Failed attempt to do a Modbus read from
Node_ID 0.

Only writes can be broadcast.

10083 Illegal Modbus Map Descriptor length

10084 Illegal Modbus Map Descriptor address

10085 Check backup station number settings...

10085

PLC_Port_Count set to 1, but Hot Standby not
configured for Mode2.

Set FieldServer parameter hs_mode to mode2

10087

Protocol specified in config file, but no such
driver is loaded.

10089 Illegal Modbus Node ID

Must be in range 1 to 255.

10102 An attempt to generate a write cache block Typically a Node has a Server_Name specified, and a