ProSoft Technology MVI94-DNP User Manual
Page 98

Reference
MVI94-DNP ♦ Flex I/O
User Manual
DNP 3.0 Server over Ethernet Communication Module
Page 98 of 131
ProSoft Technology, Inc.
December 17, 2010
Variable
Name
Data
Range
Description
IF Error
Config.
Value
Unsolicited
Response:
Y or N
Set if the slave unit will send unsolicited
response messages. If set to N, the slave
will not send unsolicited responses. If set to
Y, the slave will send unsolicited responses.
This feature requires collision avoidance on
a multi-drop network.
N
Class 1 Unsol
Resp Min:
1 to 255
events
Minimum number of events in Class 1
required before an unsolicited response will
be generated (not implemented).
10
Class 2 Unsol
Resp Min:
1 to 255
events
Minimum number of events in Class 2
required before an unsolicited response will
be generated (binary input events).
25
Class 3 Unsol
Resp Min:
1 to 255
events
Minimum number of events in Class 3
required before an unsolicited response will
be generated (analog input events).
25
Unsol Resp
Delay:
0 to 65535
millisecond
s
Maximum number of 1 millisecond intervals
to wait after an event occurs before sending
an unsolicited response message. If set to
0, only use minimum number of events.
NA
Uresp Master
Address:
0 to 65534 DNP destination address where unsolicited
response messages are sent.
65534
AI Events with
time:
Y or N
This parameter determines if the analog
input events are to be returned with a time
value. If the parameter is set to N, no time
will be returned with the event. If the
parameter is set to Y, a time will be
returned.
N
Time Sync
Before
Events:
Y or N
This parameter defines if the remote DNP
master must synchronize the time before
events are generated by the slave. If the
parameter is set to N, this synchronization
is not required. If set to Y, the
synchronization is required.
N
Initialize DNP
BO/AO:
Y or N
This parameter defines if the binary and
analog outputs are to be read from the
processor before the program starts its
normal data transfer. If the parameter is set
to N, this feature is not implemented. If the
parameter is set to Y, the feature is used
and special ladder logic must be
implemented to transfer the data from the
processor to the module.
N
Variable
Name
Data
Range
Description
IF Error
Config.
Value
[DNP Slave
Database]
This section header defines the start of the DNP slave database
definition parameter set.
Binary Inputs: 0 TO 960
Number of digital input points to configure in
the DNP slave device. Each point will be
stored as a single bit in the module
memory.
0