OBJECT
REQUES
T
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits
)
NOTES
1
Application Identifier
100 0
1
Short Floating Point
48
2
Long Floating Point
80
3
Extended Floating Point
88
101 0
1
Small Packed Binary-Coded
Decimal
16
2
Medium Packed Binary-
Coded Decimal
32
3
Large Packed Binary-Coded
Decimal
64
110 0
Not Defined
Not Defined as the
variation determines the
string length
1 to
100
Octet String
1
00, 01,
06, 07,
08, 17,
28
129,
130
00, 01,
07, 08,
17, 28
8 *
Var #
The module will return
this variation for the
points defined in the
module. The variation
determines the returned
string length.
No Object
13
Slave supports the Cold
Restart Function and will
return Obj 52, Var 2, Qual
7, Cnt 1
14
Slave supports the Warm
Restart Function and will
return Obj 52, Var 2, Qual
7, Cnt 1
20
Slave supports the
Enable Unsolicited
Function
21
Slave supports the
Disable Unsolicited
Function
23
Slave supports the Delay
Measurement & Time
Synchronization Function
and will return Obj 52, Var
2, Qual 7, Cnt 1