ProSoft Technology MVI94-DNP User Manual
Page 106

Reference
MVI94-DNP ♦ Flex I/O
User Manual
DNP 3.0 Server over Ethernet Communication Module
Page 106 of 131
ProSoft Technology, Inc.
December 17, 2010
OBJECT
REQUEST
RESPONSE
Obj
Var Description
Func
Codes
Qual
Codes
(hex)
Func
Code
s
Qual
Codes
(hex)
Data
Size
(bits
)
NOTES
7
32-Bit Delta Counter Without
Flag
129,
130
00, 01
32
Master will process this
variation
8
16-Bit Delta Counter Without
Flag
129,
130
00, 01
16
Master will process this
variation
21
0
Frozen Counter - All
Variations
1
06
32
Master will generate this
variation
1
32-Bit Frozen Counter
129,
130
00, 01
40
Master will process this
variation
2
16-Bit Frozen Counter
129,
130
00, 01
24
Master will process this
variation
3
32-Bit Frozen Delta Counter
40
4
16-Bit Frozen Delta Counter
24
5
32-Bit Frozen Counter With
Time Of Freeze
88
6
16-Bit Frozen Counter With
Time Of Freeze
72
7
32-Bit Frozen Delta Counter
With Time Of Freeze
88
8
16-Bit Frozen Delta Counter
With Time Of Freeze
72
9
32-Bit Frozen Counter
Without Flag
1
06
129,
130
00, 01
32
Master will generate and
process this variation
10
16-Bit Frozen Counter
Without Flag
1
06
129,
130
00, 01
16
Master will generate and
process this variation
11
32-Bit Frozen Delta Counter
Without Flag
32
12
16-Bit Frozen Delta Counter
Without Flag
16
22
0
Counter Change Event - All
Variations
1
06, 07,
08
Master will not generate a
request for this variation
1
32-Bit Counter Change Event
Without Time
129,
130
17, 28
40
Master will process this
variation
2
16-Bit Counter Change Event
Without Time
129,
130
17, 28
24
Master will process this
variation
3
32-Bit Delta Counter Change
Event Without Time
40
4
16-Bit Delta Counter Change
Event Without Time
24
5
32-Bit Counter Change Event
With Time
88
6
16-Bit Counter Change Event
With Time
72
7
32-Bit Delta Counter Change
Event With Time
88