Set Module Time Block (9971)
This block is constructed by the processor to send its time to the module. The
following table describes the format of this block.
Word Offset in Block Data Field(s)
Description
0
Block ID
This field contains the block identification code of
9971 for the block.
1
Year
This field contains the four-digit year for the new
time value.
2
Month
This field contains the month value for the new
time. Valid entry for this field is in the range of 1
to 12.
3
Day
This field contains the day value for the new time.
Valid entry for this field is in the range of 1 to 31.
4
Hour
This field contains the hour value for the new
time. Valid entry for this field is in the range of 0
to 23.
5
Minute
This field contains the minute value for the new
time. Valid entry for this field is in the range of 0
to 59.
6
Seconds
This field contains the second value for the new
time. Valid entry for this field is in the range of 0
to 59.
When the module receives the block, it immediately sets its time using the
information contained in the block.
Warm Boot Block (9998)
This block does not contain any data. When the processor places a value of
9998 in word 0 of the output image, the module performs a warm-start. This
involves clearing the configuration and all program status data. Finally, the
program loads the configuration information from the flash disk and begin
running. There is no positive response to this message other than the status data
being set to zero and the block polling starting over. The format of this block is
shown in the following table.
Word
Description
Length
0
9998
1
1 to 6
Not used
6
Cold Boot Block (9999)
This block does not contain any data. When the processor places a value of
9999 in word 0 of the output image, the module performs a hardware restart. This
causes the module to reboot and reload the program. There is no positive
response to this message other than the status data being set to zero and the
block polling starting over. The format of this block is shown in the following
table.
Word
Description
Length
0
9999
1
1 to 6
Not used
6